Additional Instructions
Also note the following points to prevent an accidental failure, injury, electric shock, etc.
Transportation and installation
Any person who is opening a package using a sharp object, such as a knife and cutter, must wear gloves to prevent injuries caused
by the edge of the sharp object.
When carrying products, use correct lifting gear to prevent injury.
Do not stand or rest heavy objects on the product.
Do not stack the converter unit boxes higher than the number recommended.
When carrying the converter, do not hold it by the front cover or setting dial; it may fall off or fail.
During installation, caution must be taken not to drop the converter unit as doing so may cause injuries.
Ensure that installation position and material can withstand the weight of the converter unit. Install according to the information in the
instruction manual.
Do not install the product on a hot surface.
Check the converter unit mounting orientation is correct.
The converter unit must be installed on a strong surface securely with screws so that it will not drop.
Do not install or operate the converter unit if it is damaged or has parts missing. This can result in breakdowns.
Prevent other conductive bodies such as screws and metal fragments or other flammable substance such as oil from entering the
converter unit.
As the converter unit is a precision instrument, do not drop or subject it to impact.
Use the converter unit under the following environmental conditions. Otherwise, the converter unit may be damaged.
Operating condition
Surrounding air
temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration
*1
Temperature applicable for a short time, e.g. in transit.
If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.) infiltrate into a Mitsubishi product, the product will be damaged.
Halogen-based materials are often included in fumigant, which is used to sterilize or disinfect wooden packages. When packaging,
prevent residual fumigant components from being infiltrated into Mitsubishi products, or use an alternative sterilization or disinfection
method (heat disinfection, etc.) for packaging. Sterilization or disinfection of wooden package should also be performed before
packaging the product.
Test operation and adjustment
Before starting operation, confirm and adjust the parameters. A failure to do so may cause some machines to make unexpected
motions.
Operation
When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop.
Since pressing the
make an emergency stop (power off, mechanical brake operation for emergency stop, etc).
Make sure that the start signal is off before resetting an inverter fault. Resetting a converter unit fault with the start signal ON restarts
the motor suddenly.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the product.
Do not use a magnetic contactor on the converter unit input for frequent starting/stopping of the converter unit. Otherwise, the life of
the converter unit decreases.
Use a noise filter or other means to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be
affected.
Take appropriate measures regarding harmonics. Otherwise this can endanger compensation systems or overload generators.
When parameter clear or all clear is performed, set again the required parameters before starting operations. Each parameter returns
to the initial value.
Before running a converter unit which had been stored for a long period, always perform inspection and test operation.
For prevention of damage due to static electricity, touch nearby metal before touching this product to eliminate static electricity from
your body.
FR-CC2
FR-CC2-H315 kW to H560 kW: –10 °C to +50 °C (non-freezing)
FR-CC2-H630 kW:
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95 % RH or less (non-condensing),
Without circuit board coating: 90 % RH or less (non-condensing)
*1
–20 °C to +65 °C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 1000 m above sea level for standard operation. After that derate by 3 % for
every extra 500 m up to 2500m (91 %)
2
2.9 m/s
or less at 10 to 55 Hz (directions of X, Y, Z axes)
key may not stop output depending on the function setting status, provide a circuit and switch separately to
CAUTION
–10 °C to +40 °C (non-freezing)