Connection diagram with 12-pulse rectifier power transformer
The FR-CC2 converter unit can be run with 12-pulse rectifier power supply.
Main circuit terminal
Control circuit terminal
3-phase
AC power
supply
*1
When using separate power supply for the control circuit, remove the jumpers connected to terminals R1/L11 and S1/L21.
12-pulse rectifier power transformer
For 12-pulse applications, a 12-pulse rectifier power transformer (3-winding transformer) is required (customer's pur-
chase).
To prevent imbalances in output current from the power transformers, adjust the current as follows.
– Control imbalances in output voltage from the power transformers to within the range of ±0.5 %.
– Control an imbalance in power impedance (%Z) to within the range of ±10 %.
Connection is not available