2.4 Control circuit terminals
2.4.1 Terminal layout
NC NC NC NC NC +24 SD
NC
NC NC NC SE SE
*1
For manufacturer setting. Do not use.
CAUTION
Do not use the empty terminals (NC) of the control circuit. Doing so may lead to damage of the converter unit and the
inverter.
Always connect the terminal RDA of the converter unit and the terminal MRS (X10) of the inverter, and the terminal SE
of the converter unit and the terminal PC (terminal SD in the sink logic) of the inverter. Not doing so may lead to damage
of the converter unit.
2.4.2 Wiring method
Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the
sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal.
(1) Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighbouring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
(2) Insert wires into a blade terminal, then crimp the terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Blade terminals commercially available (as of February 2012)
Cable gauge (mm²)
With insulation sleeve
0.3
AI 0,5-10WH
0.5
AI 0,5-10WH
0.75
AI 0,75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1,5-10BK
0.75 (for two wires)
AI-TWIN 2×0,75-10GY —
*2
A blade terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*3
Applicable for the terminals A1, B1, and C1 only.
NC NC
SD
RDB
RDA
IPF RSO FAN
Cable sheath stripping length
10 mm
Damaged
Blade terminal model
Without insulation
sleeve
A 0,75-10
A 1-10
A 1,5-10
NC
NC NC PC
A1
B1
PC NC NC NC NC NC NC OH
Crumpled tip
*2
For UL wire
AI 0,5-10WH-GB
AI 0,75-10GY-GB
AI 1-10RD/1000GB
AI 1,5-10BK/1000GB
∗1
∗1
C1
88R
NC
88S
RES
SD SD
RDI NC NC
NC
Unstranded
wires
Wires are not inserted
into the sleeve
Crimping tool
Manufacturer
name
Phoenix Contact
CRIMPFOX 6
Co., Ltd.
*3
WIRING