Rheem A17 Series Installation Instructions Manual page 37

Air cooled condensing units
Table of Contents

Advertisement

10.0 DIAGNOSTICS AND TROUBLESHOOTING
10.2 Status and Diagnostic Codes (cont.)
Descriptions of the EcoNet
Dual 7-Segment
LEDs Display
Code
5L - Active Protection Protector Trip
The Outdoor Control has had a protector trip
for longer than 4 hours or has tripped 3 times
during a call for cooling.
6 - Compressor Open Start Circuit
The Outdoor Control detects current in the Run
circuit but not in the Start circuit of the compres-
sor
6L - Active Protection Compressor Open Start
Circuit Lockout
The Outdoor Control detects loss of current in
the Run circuit three (3) times in one cooling call
9 - Active Protection - Line Voltage Brown Out
FLASHING
21 - Low Pressure Control Open
The Outdoor Control detects the LPC is open.
Note: The low pressure control is ignored for
the first 90 seconds of compressor operation
21L - Active Protection Low Pressure Lockout
FLASHING
2-Stage Control diagnostic codes are provided below:
TM
Diagnostic Description
Status/Possible Cause - Trouble-
shooting Information
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for open compressor internal protector
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for damaged, miswired, or wrong run
capacitor
• Check for broken wires, loose connectors, or
miswired compressor
• Check compressor windings for continuity
• Check for compressor locked rotor
The Outdoor Control has sensed line voltage has
dropped below 175V and has shut the compres-
sor off for 5 minutes. If line voltage is above 187V
after 5 minutes, the compressor is allowed to
start.
• Units has low refrigerant charge
• Indoor coil is frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Indoor blower is not running (cooling mode)
• Outdoor coil is frozen (heating mode)
• Expansion valve is not operating correctly
LPC has opened 3 times in the same call for
cooling operation, the Outdoor Control has locked
out the compressor to protect it. Outdoor Control
alternately flashes L and 21
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

A1724aj2cbA1736aj2cbA1748aj2cbA1760aj2cb

Table of Contents