Overview Of Tsodc Operation - Rheem A17 Series Installation Instructions Manual

Air cooled condensing units
Table of Contents

Advertisement

7.5 EcoNet
C- 24VAC Common from the indoor unit 24VAC
transformer
E- 1 Data: System Communications Line 1
E- 2 Data: System Communications Line 2
Low Volt Fuse
If required replace with 3 A automotive ATC style
blade fuse
Low Pressure Control (LPC Input)
Low-pressure control is factory installed
Low-pressure control is an automatic resetting device
High Pressure Control (LPC Input)
High-pressure control is factory installed
High-pressure control is an automatic resetting device
Ambient Temperature Sensor
(included with all applications)
Included with all applications
Up and Select Buttons
Up and Select buttons used to enter Test and Fault
Recall Mode
Memory Card
The memory card stores all unit information.
The unit information is called model data.
The shared data is all the information needed for
proper unit operation.
7.5.2 Overview of TSODC
Operation
Installation Verification
24V AC power must be present at the R and C termi-
nals on the control board for it to operate
Line voltage must be present at the control for the
compressor and the outdoor fan to operate.
The 7 segment LED displays a "0" for standby mode.
Standby mode indicates line voltage and 24VAC are
present at the control and there is not a command for
unit operation from the EcoNet
Thermostat.
Zero (0) displayed
The unit is in standby
2-Stage Outdoor Control (TSODC) (cont.)
TM
Control Center or
TM
7.0 COMPONENTS & CONTROLS
Command for Compressor Operation
The control has an on/off fan delay of one (1) second
for each stage of cooling.
The control ignores the low pressure control for the
first 90 seconds of compressor operation.
The dual 7-segment LED displays five (5) operational
status codes.
1) First Stage Cooling Operation
When the control received a command for first
stage cooling operation, a low case "c" is displayed
on the dual 7-segment LEDs.
Low case "c" indicates first stage cooling operation
2) Second Stage Cooling Operation
When the control received a command for second
stage cooling operation, a upper case "C" is dis-
played on the dual 7-segment LEDs.
Upper case "C" indicates second stage cooling operation
5-minute Anti-Short Cycle Timer
• The control has a built in 5-minute time delay
between cooling cycles to protect the compressor
against short cycling. The 7-segment LED will flash
"c" or "C" while the short cycle timer is active and a
command for unit operation is received.
Flashing low case c
A command for first stage cooling has been received
Flashing upper case C
A command for second stage cooling has been received
• The 5-minutes time delay can be bypassed when
a command for compressor operation is present by
pressing the UP button. The compressor will begin
operation and the 7-segment LED will stop flashing.