Rheem A17 Series Installation Instructions Manual page 13

Air cooled condensing units
Table of Contents

Advertisement

Table 2B: Refrigerant Line Sizing Chart (Metric Units)
Allowable
Allowable
Liquid Line
Vapor Line
Unit Size
Size
mm [in.]
mm [in.]
15.88 [5/8]
6.35 [1/4]
7.0 KW
7.94 [5/16]
15.88 [5/8]
[2.0 Ton]
9.53 [3/8]
15.88 [5/8]
** SEE
6.35 [1/4]
19.05 [3/4] *
NOTE 3
7.94 [5/16] 19.05 [3/4] *
9.53 [3/8]
19.05 [3/4] *
7.94 [5/16]
15.88 [5/8]
9.53 [3/8]
15.88 [5/8]
10.6 KW
7.94 [5/16]
19.05 [3/4]
[3 Ton]
9.53 [3/8]
19.05 [3/4]
12.7 [1/2]
19.05 [3/4]
9.53 [3/8]
19.05 [3/4]
14.1 KW
12.7 [1/2]
19.05 [3/4]
[4 Ton]
9.53 [3/8]
22.23 [7/8]
12.7 [1/2]
22.23 [7/8]
9.53 [3/8]
19.05 [3/4]
17.6 KW
12.7 [1/2]
19.05 [3/4]
[5 Ton]
9.53 [3/8]
22.23 [7/8]
12.7 [1/2]
22.23 [7/8]
Notes:
1) Do not exceed 46 meters linear line length.
2) *Do not exceed 15 meters vertical separation between indoor and outdoor units if the indoor unit is above the indoor unit.
3) ** 19.05mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor
unit to assure proper oil return.
4) Always use the smallest liquid line allowable to minimize refrigerant charge.
5) Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not
recommended, but are allowed.
6) Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
17 SEER 2-Stage Air-Conditioners
Use Long Line
Guidelines for
Linear Line
Lengths
Size
Greater
Than Shown
Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) * / Capacity Multiplier
Below
n/a
22
15
n/a
22
15
6
5
6
5
0
0
0
0
0
0
0
0
0
Outdoor Unit ABOVE or BELOW Indoor Unit
Equivalent Length (Meters)
< 8
8-15
8 / 0.99
15 / 0.98
9 / 0.97
8 / 0.99
15 / 0.98
15 / 0.97
8 / 0.99
15 / 0.99
15 / 0.97
8 / 1.00
15 / 0.99
9 / 0.99
8 / 1.00
15 / 0.99
15 / 0.99
8 / 1.00
15 / 0.99
15 / 0.99
8 / 0.99
15 / 0.97
15 / 0.95
8 / 0.99
15 / 0.97
15 / 0.95
8 / 1.00
15 / 0.99
15 / 0.99
8 / 1.00
15 / 0.99
15 / 0.99
8 / 1.00
15 / 0.99
15 / 0.99
8 / 0.99
15 / 0.98
15 / 0.97
8 / 0.99
15 / 0.98
15 / 0.97
8 / 1.00
15 / 0.99
15 / 0.99
8 / 1.00
15 / 0.99
15 / 0.99
8 / 0.99
15 / 0.97
15 / 0.95
8 / 0.99
15 / 0.97
15 / 0.95
8 / 1.00
15 / 0.99
15 / 0.98
8 / 1.00
15 / 0.99
15 / 0.98
4.0 INSTALLATION
16-23
24-30
31-38
1 / 0.97
NR
15 / 0.97
15 / 0.96
15 / 0.97
15 / 0.96
1 / 0.99
NR
15 / 0.99
15 / 0.98
15 / 0.99
15 / 0.98
15 / 0.93
10 / 0.91
15 / 0.93
15 / 0.91
15 / 0.98
10 / 0.97
15 / 0.98
15 / 0.97
15 / 0.98
15 / 0.97
15 / 0.95
15 / 0.94
15 / 0.95
15 / 0.94
15 / 0.98
15 / 0.98
15 / 0.98
15 / 0.98
15 / 0.93
15 / 0.91
15 / 0.93
15 / 0.91
15 / 0.98
15 / 0.97
15 / 0.98
15 /0.97
39-46
NR
15 / 0.95
15 / 0.95
NR
15 / 0.98
15 / 0.98
NR
NR
5 / 0.96
15 / 0.96
15 / 0.96
15 / 0.93
15 / 0.93
15 / 0.97
15 / 0.97
NR
NR
12 / 0.96
15 / 0.96
13