Notes on the CE Symbol for TELEPERM M AS
Notes on
Manual–Auto Stations
Updated
Technical Data
2
A filter must be inserted in the power supply lines (SIFI C, B84113–C–B30 or
similar).
In addition to the specifications in the "General Technical Data" of the System Manu-
als, the specifications on noise immunity and electromagnetic compatibility given
below apply to modules carrying the CE symbol.
The specifications are valid for systems which are assembled according to the above–
mentioned setup guidelines.

Electromagnetic Compatibility (EMC)

Radio interference suppression to EN 55011
Limit value class
Interference by conduction on AC and DC supply lines
to EN 61000–4–4 / IEC 1000–4–4 (Burst)
Interference by conduction on signal lines
to EN 61000–4–4 / IEC 1000–4–4 (Burst)
Interference by conduction on process lines
to EN 61000–4–4 / IEC 1000–4–4 (Burst)
Noise immunity to discharges of static electricity
to EN 61000–4–2 / IEC 1000–4–2 (ESD)
Noise immunity to electromagnetic HF field
amplitude modulated to
ENV 50140 / IEC 1000–4–3
Noise immunity to electromagnetic HF field
pulse modulated to ENV 50204
Noise immunity to high frequency (sinusoidal)
to ENV 50141
1) With closed doors for AS 235 and AS 235 H, open for AS 235 K
and ES 100 K
2) With AS 235 K and ES 100 K: 6 kV
1)
A
2 kV
2 kV
2 kV
2)
4 kV
1)
80 to 1000 MHz
10 V/m
80 % AM (1 kHz)
1)
900 MHz
10 V/m
50 % c.d.f.
0.15 to 80 MHz
10 V
80 % AM
C79000–Q8076–C001–03