Download Print this page

Siemens TELEPERM M AS 235 Manual page 13

Automation system / extension system

Advertisement

The diagram below shows the required protective measures against electrostatic discharge.
f
c
Standing position
b
e
a
Sitting position
5
Measurements and Modification to ESD Modules
D
Measurements on modules may only be carried out under the following conditions:
- The measuring equipment is grounded (e.g. via the PE conductor of the power supply
system) or
- when electrically isolated measuring equipment is used, the probe must be discharged
(e.g. by touching the metallic casing of the equipment) before beginning measurements.
D
Only grounded soldering irons may be used.
6
Shipping of ESD Modules
Anti-static packing material must always be used for modules and components, e.g. metalized
plastic boxes, metal boxes, etc. for storing and dispatch of modules and components.
If the container itself is not conductive, the modules must be wrapped in a conductive material
such as conductive foam, anti-static plastic bag, aluminium foil or paper. Normal plastic bags or
foils should not be used under any circumstances.
For modules with built-in batteries ensure that the conductive packing does not touch or
short-circuit the battery connections; if necessary cover the connections with insulating tape
or material.
©
Siemens AG C79000-D8076-C333-01
d
a
d
f
b
c
f
a
Standing/sitting position
a
Conductive flooring
b
Anti-static table
c
Anti-static shoes
d
Anti-static coat
e
Grounding wrist strap
f
Grounding connection of the cabinets
ESD Guidelines
d
e
f f
3

Advertisement

loading

This manual is also suitable for:

Teleperm m es 100 k6ds2 1246ds2 127