Johnson Controls TEC2103-1 Installation Instructions Manual page 4

Networked multi-stage thermostat
Hide thumbs Also See for TEC2103-1:

Advertisement

Table 1: N2 Bus Objects
Point Name
a
Room Temp
Aux Temp / Outdoor Temp
a, g
Heating SP
(Occupied Heating SP)
a, g
Cooling SP
(Occupied Cooling SP)
a, g
Setback Heating SP
(Unoccupied Heating SP)
a, g
Setback Cooling SP
(Unoccupied Cooling SP)
Minimum Heat SP
a
Maximum Heat SP
a
Minimum Cool SP
Maximum Cool SP
a
Fan
a
Mode
a
Occupancy
W1 State
W2 State
Y1 State
Y2 State
G State – Fan
a, c
Temp Units
(Local Display Only)
Continued on the next page . . .
4
TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions
TEC Point
N30/NAE
Type/
Object
Address
Type
ADI-1
N2 AI
a
ADI-2
N2 AI
ADI-3
N2 AO
ADI-4
N2 AO
ADI-5
N2 AO
ADI-6
N2 AO
ADI-7
N2 AI
ADI-8
N2 AO
ADI-9
N2 AI
ADI-10
N2 AO
BD-1
N2 BO
BD-2
N2 MSO
BD-3
N2 BO
BD-4
N2 BI
BD-5
N2 BI
BD-6
N2 BI
BD-7
N2 BI
BD-8
N2 BI
BD-9
N2 BO
BAS Model
Override Range
Point Type
CSAD
32 to 122°F (0 to 50°C)
CSAD
-40 to 122°F (-40 to 50°C)
CSAD
40 to 90°F (4.5 to 32°C)
CSAD
54 to 100°F (12 to 37.5°C)
CSAD
40 to 90°F (4.5 to 32°C)
CSAD
54 to 100°F (12 to 37.5°C)
CSAD
40°F (4.5°C)
CSAD
40 to 90°F (4.5 to 32°C)
CSAD
54 to 100°F (12 to 37.5°C)
CSAD
100°F (37.5°C)
CSBD
0 = Auto, 1 = On
d, e
CSMS
0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
CSBD
0 = Unoccupied, 1 = Occupied
CSBD
0 = Off, 1 = On
CSBD
0 = Off, 1 = On
CSBD
0 = Off, 1 = On
CSBD
0 = Off, 1 = On
CSBD
0 = Off, 1 = On
0 = °C, 1 = °F
See
Footnote c.