Setting the Fan Control (Fan cont)
This parameter controls how the fan activates in
response to a call for heating.
When the fan is in Auto Mode (as selected on the Main
User Menu):
select on to enable the thermostat to control the
fan on a call for heating or cooling
select off to energize the fan on a call for cooling
only by the thermostat. On a call for heating, the
fan is controlled by the equipment fan limit control.
To set the fan control while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the fan control
prompt appears in the display. Press YES to enter
the fan control menu.
2. Using the UP/DOWN arrow keys, select on or off.
Press YES to store the selection.
The display now shows the fan delay prompt. See the
Setting the Fan Delay (Fan del) section for
instructions.
Setting the Fan Delay (Fan del)
The fan delay extends the fan operation by
60 seconds after the call for heating or cooling has
ended. This feature is only active when the fan is in
the Auto mode.
To enable the fan delay while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the fan delay
prompt appears in the display. Press YES to enter
the fan delay menu.
2. Using the UP/DOWN arrow keys, select on or off.
Press YES to store the selection.
The display now shows the N2 address prompt. See
the Setting the N2 Address (N2 addr) section for
instructions.
Setting the N2 Address (N2 addr)
To adjust the N2 address (adjustable from 1 to 253)
while in the Installer Configuration Menu:
1. Answer NO to all prompts until the setting the
N2 address prompt appears in the display. Press
YES to set the address.
2. Use the UP/DOWN arrow keys to display the
desired address. Press YES to store the address.
The display now shows the temporary occupancy time
prompt. See the Establishing the Temporary
Occupancy Time (ToccTime) section for instructions.
Note: Pressing the YES and NO keys
simultaneously for 5 seconds on the user interface of
the TEC2103-1 temporarily displays the N2 address of
the thermostat.
Establishing the Temporary Occupancy Time
(ToccTime)
The temporary occupancy is the length of time the
occupied mode setpoints are used when the override
function is enabled (the override function can be
enabled from the Main User Menu when the
thermostat is in unoccupied mode or from one of
the digital inputs) or a temporary setpoint is entered.
The range is adjustable from 0 to 12 hours.
To change the temporary occupancy time while in the
Installer Configuration Menu:
1. Answer NO to all prompts until the temporary
2. Use the UP/DOWN arrow keys to adjust the length
The display now shows the room sensor calibration
prompt. See the Room Air Sensor Calibration (Cal RS)
section for instructions.
Room Air Sensor Calibration (Cal RS)
An offset can be added or subtracted to the actual
displayed room temperature as needed. The range is
±5.0 F° (±2.5 C°), adjustable in increments of 1 F°
(0.5 C°).
To change the room sensor calibration/offset while in
the Installer Configuration Menu:
1. Answer NO to all prompts until the room sensor
2. Use the UP/DOWN arrow keys to adjust the
The display now shows the auxiliary
temperature/outdoor air sensor calibration prompt.
See the Auxiliary Temperature/Outdoor Air Sensor
Calibration (Cal OS) section for instructions.
TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions
occupancy time prompt appears in the display.
Press YES to enter the temporary occupancy time
menu.
of time the temporary occupancy setpoint should
be in effect. Press YES to store the time.
calibration prompt appears in the display. Press
YES to enter the room sensor calibration menu.
correction that should be applied to the sensor
reading. Press YES to store the offset.
11