3 Engineering
4. Under "Logic modules > Limit monitor > Limit monitor 4", parameterize the limit
value function block for the cos φ lower limit in forward flow direction.
The limit monitor should only be active when the motor is running and after the
start procedure is complete ("if motor is running, except TPF, with startup
override (run+)").
The limit should be specified in %, based on the motor current at the input
plug. Add a label is necessary.
Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058,
V2.0,
09/2020
52