Selection and protection of a motor
(4)
Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
<Operating procedure>
1) Set Pr. 71 according to the motor used.
Mitsubishi standard motor
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Other manufacturer's
standard motor
Other manufacturer's
constant-torque motor
∗1
For other settings of Pr.71, refer to page 125.
2) In the parameter setting mode, read the following parameters and set desired values.
Parameter
Number
82
Motor excitation current
90
Motor constant (R1)
91
Motor constant (R2)
92
Motor constant (L1)
93
Motor constant (L2)
94
Motor constant (X)
859
Torque current
REMARKS
When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants are used.
As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting:
Setting example To slightly increase Pr. 90 value (5%)
132
Motor
SF-JR
SF-JR 4P 1.5kW or less
SF-HR
Others
SF-JRCA 4P
SF-HRCA
Others (SF-JRC, etc.)
-
-
Name
Setting Range
0 to ****, 9999
0 to ****, 9999
0 to ****, 9999
0 to ****, 9999
0 to ****, 9999
0 to ****, 9999
0 to ****, 9999
When Pr. 90 is displayed as "2516",
set 2642 (2516 x 1.05=2641.8) in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addition of a given
value to the displayed value has no significance.)
Pr. 71 Setting ∗1
4
24
44
4
14
54
14
4
14
Setting
Initial
Increments
Value
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999
1
9999