Check code
[F07] / [18]
(Current code / AI-NET)
This error code means detection of Open/Short of TL sensor.
Check disconnection of circuit for connection of connector (TL sensor: CN521, White) and characteristics of
sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P .C. board.
Check code
[F08] / [1b]
(Current code / AI-NET)
This error code means detection of Open/Short of TO sensor.
Check disconnection of circuit for connection of connector (TO sensor: CN507, Yellow) and characteristics of
sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P .C. board.
Check code
[F10] / [0C]
(Current code / AI-NET)
This error code means detection of Open/Short of TA sensor.
Check disconnection of circuit for connection of connector (TA sensor: CN104, White) and characteristics of
sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace indoor P .C. board.
Check code
[F12] / [A2]
(Current code / AI-NET)
This error code means detection of Open/Short of TS1 sensor.
Check disconnection of circuit for connection of connector (TS1 sensor: CN504, White) and characteristics of
sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P .C. board.
Check code name
TL sensor error
Check code name
TO sensor error
Check code name
Indoor TA sensor error
Check code name
TS1 sensor error
89
Cause of operation
TL sensor Open/Short
Cause of operation
TO sensor Open/Short
Cause of operation
TA sensor Open/Short
Cause of operation
TS1 sensor Open/Short