11
APPLICABLE CONTROLS
2
Procedure
UNIT LOUVER
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings.
The fan of the selected unit runs and the louvers
start swinging. You can confirm the indoor unit for
which you want to change settings.
3
Procedure
Using "TEMP ."
/
buttons, specify CODE No.
[
].
4
Procedure
Using timer "TIME"
/
buttons, select SET
DATA [
].
5
Procedure
SET
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
2
from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
SET
Use
button to clear the settings.
SET
To make settings after
button was pushed,
2
repeat from Procedure
.
6
Procedure
TEST
When settings have been completed, push
button to determine the settings.
TEST
When
button is pushed, "SETTING (
)"
SETTING
flashes and then the display content disappears
and the air conditioner enters the normal stop
mode.
(While "SETTING (
)" is flashing, no operation
SETTING
of the remote controller is accepted.)
n Change of lighting time of filter sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [01].
4
• For the [SET DATA] in Procedure
, select the
SET DATA of filter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
n To secure better effect of heating
When it is difficult to obtain satisfactory heating
due to installation place of the indoor unit or
structure of the room, the detection temperature of
heating can be raised. Also use a circulator, etc. to
circulate heat air near the ceiling.
Follow to the basic operation procedure.
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [06].
4
• For the SET DATA in Procedure
, select the
SET DATA of shift value of detection temperature
to be set up from the table below.
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C
0003
+3°C (Factory setting)
0004
+4°C
0005
+5°C
0006
+6°C
n Adjustment of air direction
1. Using the remote controller switch, change the up/down air direction by moving the horizontal louver.
2. Adjust the right/left air direction by bending the vertical grille inside of the air outlet port with hands.
REQUIREMENT
Do not touch the horizontal louver directly with hands; otherwise a trouble may be caused.
For handling of the horizontal louver, refer to "Owner's Manual" attached to the outdoor unit.
n Group control
In a group control, a remote controller can control up to maximum 8 units.
• The wired remote controller only can control a group control.
The wireless remote controller is unavailable for this control.
• For cabling procedure and cables of the individual line (Identical refrigerant line) system, refer to
"Electric work" in this Manual.
• Cabling between indoor units in a group is performed in the following procedure.
Connect the indoor units by connecting the remote controller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual attached to the outdoor unit.
NOTE
Net work adapter (Model TCB-PCNT20E) can not connect to this High Wall type air conditioner.