Toshiba SUPER MMK-AP0073H (IN) Service Manual page 67

Hide thumbs Also See for SUPER MMK-AP0073H (IN):
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
controller
Check code
Sub-code
L03
L04
L04
L05
L06
L06
No. of indoor units with
priority
L07
L08
L08
L09
L10
L10
L20
L28
L28
L29
L29
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or
communication error
between IPDU and
I/F P .C. board, or outdoor
I/F P .C. board error
Detected
AI-NET
Check code name
position
central control
remote controller
96
Indoor
Duplicated indoor center units
96
I/F
Duplicated outdoor line address
96
I/F
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
96
I/F
Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)
99
Indoor
Group line in individual indoor unit.
99
Indoor
Indoor group / address unset
46
Indoor
Indoor capacity unset
88
I/F
Outdoor capacity unset
98
AI-NET,
Duplicated central control addresses
Indoor
46
I/F
Quantity over of connected outdoor
units
CF
I/F
IPDU quantity error
Status
Error detection condition
Corresponding
There are multiple center
• Check indoor address.
unit only stops.
units in a group.
• Check the change of remote controller connection
All stop
Line address setup is
• Check line address.
duplicated against the
outdoor unit in different
refrigerant pipe system.
All stop
Indoor units with priority
• Check display of indoor unit with priority.
were duplicated.
All stop
Indoor units with priority
• Check display of indoor unit with priority and outdoor
were duplicated.
Corresponding
At least one indoor unit
• Check indoor address.
unit only stops.
connected to a group
existed in the individual
indoor units.
Corresponding
Address was not yet set up.
• Check indoor address.
unit only stops.
[Note]
After installation, this code is displayed when the power
is firstly turned on.
Corresponding
Indoor unit capacity was
Set up indoor capacity. (DN=11)
unit only stops.
unset.
All stop
On the I/F P .C. board for
Check model setup on outdoor I/F P .C. board A'ssy for
service, jumper line was not
service.
cut according to the model.
All stop
Duplicated central control
• Check central control address.
addresses
• Check network adaptor P .C. board.
All stop
There were more than four
• Check No. of connected outdoor units.
outdoor units.
• Check communication line between outdoor units.
• Check outdoor P .C. board (I/F) error.
All stop
No. of IPDU units detected
• Check model setup for outdoor I/F service P .C. board.
when power was turned on
• Check connection of UART communication connector.
were less.
• Check IPDU, fan IPDU, and I/F P .C. board error.
[Note]
UART: Universal Asynchronous Receiver Transmitter.
Check item (position)
(Group/individual) after indoor address setup.
unit.
(In case of AI-NET)
(Max. 4 units per 1 system)