FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SERIAL COMMUNICATION BINARY INPUT DATA
This data can be read using a BACnet or Modbus network connection and can NOT be modified using this connec-
tion. The Modbus Register Address for these points is 1281 + BI #.

TABLE 40 - SERIAL COMMUNICATION BINARY INPUT DATA

BI
BACNET NAME
1
S1_ALARM
2
S2_ALARM
3
EVAP_HTR
4
EVAP_PUMP
5
SI_C1_RUN
6
S2_C1_RUN
7
S1_LLSV
8
S1_MODE_SV
9
S1_HGBV
10
S1_BHS
11
S1_C2_RUN
12
S2_C2_RUN
13
S2_LLSV
14
S2_MODE_SV
15
LEAD_SYS
16
S1_C3_RUN
17
S2_C3_RUN
18
CH_LIQ_TYPE
19
AMB_MODE
20
CNTL_MODE_
21
DATA_UNIT
22
AUTO_LL
JOHNSON CONTROLS
BINARY INPUT DESCRIPTION
SYS 1 ALARM
SYS 2 ALARM
EVAPORATOR HEATER STATUS
EVAPORATOR PUMP STATUS
SYS COMP 1 RUN
SYS 2 COMP 1 RUN
SYS 1 LIQUID LINE SOLENOID VALVE
SYS 1 MODE SOLENOID VALVE (HP ONLY)
SYS 1 HOT GAS BYPASS VALVE
BIVALENT HEAT SOURCE (HP ONLY)
SYS 1 COMP 2 RUN
SYS 2 COMP 2 RUN
SYS 2 LIQUID LINE SOLENOID VALVE
SYS 2 MODE SOLENOID VALVE (HP ONLY)
LEAD SYSTEM (0 = SYS 1, 1 = SYS 2)
SYS 1 COMP 3 RUN
SYS 2 COMP 3 RUN
CHILLED LIQUID TYPE (0 = WATER, 1 = GLYCOL)
AMBIENT CONTROL MODE (O = STD AMB, 1 = LOW AMB)
LOCAL / REMOTE CONTROL MODE (0 = LOCAL, 1 = REMOTE)
UNITS (0 = IMPERIAL, 1 = SI)
LEAD / LAG CONTROL MODE (0 = MANUAL, 1 = AUTO)
SECTION 10 – MAINTENANCE