Table 30 - Pressure Transducers - York YLUA0248 Series Installation Operation & Maintenance

Air-cooled scroll condensing units
Table of Contents

Advertisement

FORM 150.73-NM2
ISSUE DATE: 09/07/2020

TABLE 30 - PRESSURE TRANSDUCERS

0-400 PSIG SUCTION
PRESSURE TRANS-
DUCER
PRESSURE
VOLTAGE
PSIG
VDC
0
0.5
50
1.0
100
1.5
150
2.0
200
2.5
250
3.0
300
3.5
350
4.0
400
4.5
Red Wire = 5V, Black wire = 0V, White/Green Wire = signal
TEST POINTS:
Suction Pressure:
System 1: ............................................... Microboard J7-10 to J7-9
System 2: ............................................... Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ............................................... Microboard J7-11 to J7-7
System 2: ............................................... Microboard J9-11 to J9-7
V = (Pressure in PSIG x .01) + .5
V = (Pressure in BARG x .145) + .5
where V = dc voltage output
Pressure = pressure sensed by transducer
The I/O board connections for the Discharge
Transducers:
System 1 Discharge Transducer
J7-6 = +5VDC regulated supply to transducer.
J7-11 = VDC input signal to the microboard. See the
formula above for voltage readings that corre-
spond to specific discharge pressures.
J7-7 = +5VDC return
J7-2 = drain (shield connection = 0VDC)
JOHNSON CONTROLS
0-600 PSIG DISCHARGE
PRESSURE TRANS-
DUCER
PRESSURE
VOLTAGE
PSIG
VDC
0
0.5
75
1.0
150
1.5
225
2.0
300
2.5
375
3.0
450
3.5
525
4.0
600
4.5
or
SECTION 9 – SERVICE AND TROUBLESHOOTING
System 2 Discharge Transducer
J9-6 = +5VDC regulated supply to transducer.
J9-11 = VDC input signal to the microboard. See the
formula above for voltage readings that correspond to
specific discharge pressures.
J9-7 = +5VDC return
J9-2 = drain (shield connection = 0VDC)
The suction transducers have a range from 0 to 400
PSIG (27.5 barg). The output will be linear from
0.5VDC to 4.5VDC over the 400 PSIG (27.5 barg)
range. Following is a formula that can be used to verify
the voltage output of the transducer. All voltage read-
ing are in reference to ground (unit case).
V = (Pressure in PSIG x .02) + .5
or
V = (Pressure in barg x .29) + .5
where V = dc voltage input to micro
Pressure = pressure sensed by transducer
Following are the I/O board connections for the Suc-
tion Transducer:
System 1 Suction Transducer
J7-5 = +5VDC regulated supply to transducer.
J7-10 = VDC input signal to the microboard.
See the formula above for voltage readings that c o r -
respond to specific suction pressures.
J7-9 = +5VDC return
J7-1 = drain (shield connection = 0VDC)
System 2 Suction Transducer
J9-5 = +5VDC regulated supply to transducer.
J9-10 = VDC input signal to the microboard.
See the formula above for voltage readings that c o r -
respond to specific suction pressures.
J7-9 = +5VDC return
J7-11 = drain (shield connection = 0VDC)
9
141