Table 29 - Discharge Air Temp. Sensor Temperature/Voltage/Resistance Correlation - York YLUA0248 Series Installation Operation & Maintenance

Air-cooled scroll condensing units
Table of Contents

Advertisement

SECTION 9 – SERVICE AND TROUBLESHOOTING
TABLE 29 - DISCHARGE AIR TEMP. SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP °F
VOLTAGE RESISTANCE
0
1.71
2
1.78
4
1.85
6
1.93
8
2.00
10
2.07
12
2.15
14
2.22
16
2.30
18
2.37
20
2.45
22
2.52
24
2.59
26
2.67
28
2.74
30
2.81
32
2.88
34
2.95
36
3.02
38
3.08
40
3.15
42
3.21
44
3.27
46
3.33
48
3.39
50
3.45
52
3.51
54
3.56
56
3.61
58
3.67
60
3.72
62
3.76
64
3.81
66
3.86
68
3.90
70
3.94
72
3.98
74
4.02
76
4.06
78
4.10
80
4.13
140
TEMP °C
25619
-18
24046
-17
22580
-16
21214
-14
19939
-13
18749
-12
17637
-11
16599
-10
15629
-9
14721
-8
13872
-7
13077
-6
12333
-4
11636
-3
10982
-2
10370
-1
9795
0
9256
1
8750
2
8276
3
7830
4
7411
6
7017
7
6647
8
6298
9
5970
10
5661
11
5370
12
5096
13
4837
14
4593
16
4363
17
4145
18
3941
19
3747
20
3564
21
3392
22
3228
23
3074
24
2928
26
2790
27
Discharge Air Temperature Sensor
J6-5 =
+5 VDC regulated supply to sensor.
J6-8 =
VDC input signal to the microboard.
See Table 31 for voltage readings that
correspond to specific discharge tem-
peratures.
J6-2 =
drain (shield connection = 0 VDC)
Analog Inputs – Pressure
Refer to the unit wiring diagram. Pressure inputs are
connected to the microboard on plugs J7 and J9. These
analog inputs represent varying dc signals correspond-
ing to varying pressures. All voltages are in reference
to the unit case (ground).
System 1 discharge and suction pressures will be con-
nected to J7 of the microboard. System 2 discharge and
suction pressure transducers will be connected to J9 of
the microboard.
The discharge transducers are optional on all units. If
the discharge transducers are not installed, no connec-
tions are made to the microboard and the discharge
pressure readout on the display would be zero.
The suction pressure transducers are standard on all
YLUA's. The suction pressure transducers have a
range of 0 to 400 PSIG. The output will be linear from
0.5VDC to 4.5VDC over the 400 PSIG (27.5 barg)
range.
The discharge transducers have a range from 0 to
650 PSIG. The output will be linear from 0.5VDC to
4.5VDC over the 650 PSIG (41.25 barg) range. Fol-
lowing is the formula that can be used to verify the
voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
JOHNSON CONTROLS