Mounting IO-Link I/O modules on a non-conductive surface

Requirement
Non-conductive surface for mounting of the module
Required tool
To connect to functional ground, you need the following tool:
• Screwdriver or hexagon socket size 3
• Stripping tool
• Crimp tool
Required accessories:
To connect to functional ground in the case of a non-conductive mounting surface, you need
the following accessories:
• 2 x 4 mm fixing screws
• Cable lug, suitable for 4 mm screws
• Grounding cable (braided copper cable) with a minimum cross section of 4 mm
Mounting
To connect IO-Link I/O modules to functional ground, proceed as follows:
1. Drill two fastening holes.
2. Strip the grounding cable.
3. Fasten the cable lug to the grounding cable.
4. Screw the module and the cable lug with the 4 mm fastening screws using a torque of
1.2 Nm.