Commissioning
6.4 Modbus address register
Wiring test results
Address
Number
of regis-
Hex
Decimal
ters
1F20
7968
2
The wiring is correct if the result is 0 or no bit is active.
Parameter setup
Parameters are read and changed in accordance with the following rules:
Address
Number
of regis-
Hex
Decimal
ters
5000
20480
1
5001
20481
1
5002
20482
1
5004
20484
1 ... 28
2F01
12033
1
Accessed via the function codes 0x04 (read) or 0x06 (write).
1)
Accessed via 0x04 (read), 0x06 (write), or 0x16 (multiwrite).
2)
90
Format
Access
Active bit
UINT32
R
0
UINT32
R
1
UINT32
R
2
UINT32
R
3
UINT32
R
4
UINT32
R
5
UINT32
R
6
UINT32
R
7
UINT32
R
8
UINT32
R
9
UINT32
R
10
UINT32
R
11
UINT32
R
12
UINT32
R
13
UINT32
R
14
UINT32
R
15
UINT32
R
16
Format
Access
Unit
UINT16
RW
–
UINT16
RW
–
UINT16
RW
–
UINT16
RW
–
UINT16
RW
–
Measured variable
Voltage L1N
Voltage L2N
Voltage L3N
Current L1
Current L2
Current L3
Incorrect phase sequence
Phase unbalance
Current transformer L1 inverted
Current transformer L2 inverted
Current transformer L3 inverted
Current transformers L1 to L2
Current transformers L1 to L3
Current transformers L2 to L1
Current transformers L2 to L3
Current transformers L3 to L1
Current transformers L3 to L2
Factor
Measured variable
–
Menu Number selection
–
Menu Number selection
–
Parameter Number selection
–
Parameter value
0.1
Write to Flash memory
Equipment Manual, 09/2020, 2514284147-04
1)
1)
1)
2)
1)
7KT16 energy meter