Keypad Functions - Siemens SENTRON 7KT PAC1600 Equipment Manual

Energy meter
Hide thumbs Also See for SENTRON 7KT PAC1600:
Table of Contents

Advertisement

Basic properties
• DIN rail enclosure, 4 MW (72 mm wide)
• Direct connection for currents up to 80 A
• LCD with backlighting
• 6-digit counter with one place after the decimal point
• 3 keys for selecting measured variables and for setting parameters
• Active and reactive energy meter
• Partial meter for active and reactive energy
• Three hour counters
• Pulse LED for active energy consumption
• Display of instantaneous consumption (active power)
• Optional: RS 485, M-Bus or S0 interface
• Optional: MID certification
• AC input for tariff selection
3.4.1

Keypad functions

You can operate the device with three keys.
The keys are assigned different functions.
The functions of the keys depend on the menu level currently in use.
"Increase" and "Decrease" keys
• Press the "Increase" or "Decrease" keys:
– Scroll between screens
– Select available options on the display
– Change (increase/decrease) settings
• Press the "Increase" and "Decrease" keys simultaneously (> 5 s): Opens and closes the
various display and setup menus.
"Next" key
• Scroll to subpages
• Confirm selected options
• Switch between display modes
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Description
3.4 Three-phase devices 80 A
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 7kt16Sentron 7kt pac 1600

Table of Contents