Daikin UWL-B5 Series Catalogue/Engineering Data page 37

Water source modular chiller (heat pump)
Table of Contents

Advertisement

Functions
MC305 is a wall-mounted LCD controller which directly controls air conditioners through keys on its panel.
1) Features
Two operation modes: heating/cooling (Note: operation modes can only be switched when the unit is off)
For air cooling chiller, temperature setting range for inlet water: cooling 10ºC~25ºC, heating 25ºC~50ºC; For
water cooled chiller, temperature setting range for inlet water: cooling 9ºC~25ºC (-10ºC~10ºC for low water
temperature unit), heating 25ºC~50ºC.
■ Temperature setting range for anti-freeze: 2ºC~5ºC.
■ A LED is used to indicate the status of the unit (ON/OFF).
■ Timed ON/OFF: a timing schedule can be set for a maximum of 7 days with up to 4 timed actions each day.
■ Real-time clock.
■ Error code display speeds up diagnosis.
■ Blue back light will shine 8 second if any key is pressed, it makes sure that we can browse or modify
parameters even in dark.
2) Use specification
Display compressor status
This
area
displays
the
compressor status.
When 1 is displayed, compressor 1#
is operating. If nothing is displayed,
no compressor is operating.
Multi-function display area
This area can display the unit error
code, inlet water temperature and
outlet water temperature.
Mode display
This area displays the operating mode
at the moment.
Time and password display
In normal case, this area displays the
current clock. When you press the
"Password"
key,
it
will
adjusted password. When you press
the "Week and Time setting" key, it
will display adjusted time.
"Resetting" key
You can use a needle tool to push the
small button to power on and reset
the controller
"▲ ▲ ▲ ▲ " and "▼ ▼ ▼ ▼ " keys
1. Change the displaying content of
multi-functional
LCD.
according to the sequence in the item
list.
2. Press the key to change the set
temperature.
"Enter" key
It is used to set the clock, timing,
temperature, password, unit number,
and other parameters.
36
current
Cooling
display
Display
Compressor
Cooling
Unit No.
Inlet Water
Temperature
Unit
Mode
Enter
Password
Timer
ON/OFF display
This area displays whether the current
unit is ON or OFF.
Unit No. display
This area displays the current unit No.
(the
corresponding
displayed
according
numbering principle).
ON
ON/OFF
Press the "ON/OFF" key to turn on
(the RUN indicator is on) or turn off
(the RUN indicator is off) a unit.
"Week and Time setting" key
You can use a needle tool to push the
small button. The time and password
area will display the corresponding
week and time options. Then, press
the "▲" and "▼" keys to set the week
and time.
"Mode setting" key
You can press the "Mode" key to
switch between the cooling mode
and heating mode. Note that the
mode can be switched only when the
unit is turned off.
"Unit" key
Press the "Unit" key to switch the next
unit. Select different units and view
their status respectively.
"Timer" key
You can set different time for turning
on/off different units.
"Password" key
Press the " Password " key to
display "Enter password" and "----" in
the lower left box of the LCD, and
press the "▲" or "▼" key to
change the value. After selection,
press the " Enter " key. Time is
displayed in the display box.
unit code
is
to
the
DIP

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uwl030b5Uwl040b5

Table of Contents