Heating capacity and heating power input performance table
UWL030B5
10
13
15
17
Heat
18
source
20
EWT(ºC)
23
25
27
30
UWL030B5
10
13
15
17
Heat
18
source
20
EWT(ºC)
23
25
27
30
Note: The parameters are tested base on unit rated water flow.
10
25
28
30
117.5
118.4
118.9
127
127.7
128
133.1
133.7
133.8
138.9
139.4
139.4
141.7
142.1
142.2
147.2
147.5
147.4
155.1
155.1
154.9
160
159.9
159.6
164.7
164.5
164.1
171.4
170.9
170.4
25
28
30
16.3
18.2
19.4
16.6
18.4
19.7
16.8
18.6
19.9
17.1
18.9
20.1
17.2
19
20.2
17.5
19.2
20.4
17.9
19.6
20.7
18.2
19.8
20.9
18.5
20.1
21.2
18.9
20.5
21.6
Using side LWT(ºC)
33
36
40
Cpapacity (kW)
119.2
119.2
118.5
128.1
127.9
127
133.8
133.4
132.3
139.3
138.7
137.5
141.9
141.3
139.9
147
146.3
144.7
154.3
153.4
151.5
158.9
157.8
155.7
163.2
162
159.8
169.3
167.9
165.4
Using side LWT(ºC)
33
36
40
Power (kW)
21.3
23.2
25.8
21.5
23.4
25.9
21.7
23.5
25.9
21.8
23.6
26
21.9
23.7
26.1
22.1
23.9
26.2
22.4
24.1
26.4
22.6
24.3
26.5
22.8
24.5
26.7
23.2
24.8
26.9
45
48
50
116.8
115.3
114.1
124.9
123.2
121.9
130.1
128.2
126.8
134.9
132.9
131.4
137.3
135.2
133.7
141.9
139.7
138
148.3
145.9
144
152.3
149.7
147.8
156.1
153.3
151.3
161.3
158.4
156.2
45
48
50
28.9
30.8
32.1
28.9
30.8
32
29
30.8
32
29
30.8
32
29.1
30.8
32
29.1
30.9
32
29.2
30.9
32.1
29.3
31
32.1
29.4
31.1
32.2
29.6
31.2
32.3