Installation
Working Condition
Item
Power supply voltage
Power supply frequency
Variations between phases
Air quality
Flow rate of chilled water
Pressure of chilled water
Quality of chilled water
Installation site
Ambient temp.
Relative humidity
Note:
1.
The unit is strictly tested before delivery and can work safely in the rated working conditions.
2.
For the performance of the unit in different working conditions, please refer to performenc data.
3.
This is the normal operating temperature range for the unit. Beyond this temperature range, the unit
can only operate for a short moment before a failure alarm is triggered.
16
Rated voltage ±10%
Rated frequency ±1%
Rated voltage ±2%
Must not contain solute that can corrode copper, aluminum or iron.
0.5 - 2.0m/s
< 1.0Mpa
"Must not contain solute that can corrode copper, iron, or welding material.
For details on the water quality requirements, see Water Quality
Management. "
Take anti-snow and ventilation measures as required.
Refer to the Performae Data.
<90%
Description