2
SPECIFICATIONS
This section describes the performance specifications.
2.1

Performance Specifications of CC-Link IE TSN

The following table lists the performance specifications of CC-Link IE TSN of the RJ71GN11-T2.
Item
Maximum number of link points per network
Maximum number of link points per
station
Transient transmission capacity
*2
Safety communications
Communication speed
Minimum synchronization cycle
Authentication Class
Network topology
Communication cable
Maximum station-to-station distance
Maximum number of connectable CC-Link IE TSN Communication
Software
Overall cable distance
Maximum number of connectable stations
Maximum number of networks
Communication method
Multicast filter
Number of occupied I/O points
Internal current consumption (5VDC)
External dimensions
Weight
*1 The maximum number of points for all link devices may not be used simultaneously depending on the number of slave stations, or the
number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings".
*2 For the RJ71GN11-T2, availability depends on the firmware version. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
2 SPECIFICATIONS
18
2.1 Performance Specifications of CC-Link IE TSN
Description
*1
RX
16K points (16384 points, 2K bytes)
RY
16K points (16384 points, 2K bytes)
RWr
8K points (8192 points, 16K bytes)
RWw
8K points (8192 points, 16K bytes)
LB
32K points (32768 points, 4K bytes)
LW
16K points (16384 points, 32K bytes)
Master station and
RX
16K points (16384 points, 2K bytes)
local stations
RY
16K points (16384 points, 2K bytes)
RWr
8K points (8192 points, 16K bytes)
RWw
8K points (8192 points, 16K bytes)
LB
32K points (32768 points, 4K bytes)
LW
16K points (16384 points, 32K bytes)
Maximum 1920 bytes
Maximum number of safety
connections per station
Maximum number of safety
1 connection
connections per the same
communication destination
station
Maximum number of link
points per safety connection
125.00s
Authentication Class B device
Line topology, star topology, coexistence of line and star topologies, ring topology
Ethernet cable which satisfies standard: ( Page 58 Wiring products)
100m
2
Line topology
12000m (when 121 stations are connected)
Ring topology
12100m (when 121 stations are connected)
Others
Depends on the system configuration.
121 stations (master station: 1, slave stations: 120, extension modules included)
239
Time sharing method
Supported
32 points (I/O assignment: Intelligent 32 points)
0.81A
Height
106mm (Base unit mounting side: 98mm)
Width
27.8mm
Depth
110mm
0.2kg
• Master station: 120 connections
• Local station: 1 connection
• Input: 8 words
• Output: 8 words
• 1Gbps
*2
• 100Mbps
*2