Name (Model)
● Attachment to enable installation of FR-CS80 series on DIN rail.
●Selection table
Attachment Model
FR-UDA01
FR-UDA02
● Approximate dimension
DIN rail mounting
attachments
FR-UDA[]
● The EMC compliant EMC filter (EN61800-3 2nd Environment Category C3) is a filter compliant with the EU EMC Directive
(EN61800-3 2nd Environment Category C3).
EMC filter Model
SF1306
FR-E5NF-H3.7K
FR-E5NF-H7.5K
FR-S5NFSA-1.5K
EMC Directive compliant
EMC filter
EMC filter
SF
Model
FR-E5NF-H[]K
(400V class)
FR-S5NFSA-[]K
(200V class)
SF1175
(Note) This is a sample outline dimension drawing. The shape differs by the model.
●Prevention of leakage current
Take the following actions to prevent malfunction of peripheral devices or an electric shock caused by leakage current.
1) Earth (ground) the EMC filter before connecting the power supply. When doing so, confirm that earthing (grounding) is
securely performed through the earthing (grounding) part of the enclosure.
2) Select an appropriate earth leakage circuit breaker or an earth leakage relay by considering leakage current of the EMC filter.
Note that earth leakage circuit breaker may not be used in some cases such as when leakage current of the EMC filter is too
large. In that case, use an earth leakage relay with high sensitivity. When both of earth leakage circuit breaker and earth
leakage relay cannot be used, securely earth (ground) as explained in 1).
Inverter Capacity
FR-CS84
012, 022
025, 042
036, 050, 080
070, 100
FR-UDA01
68
67
Hook
3-M4 0.7 screw
Applicable inverter
model
W
FR-CS82S-025, 042
110
FR-CS84-012 to 080
140
FR-CS84-120, 160
220
FR-CS82S-070, 100
110
Applicable
Intercompatibility
attachment ∗1
inverter model
FR-CS84-230,
FR-AAT02
295
∗1
Depth is 12mm deeper when an intercompatibility attachment is installed.
∗2
Leakage current for one phase of three-phase three-wire star-connection power supply.
Leakage current for all phases of three-phase three-wire delta-connection power supply is
three times greater than the indicated value.
Specifications, Structure, etc.
FR-CS82S
FR-UDA02
108
67
15
4-M4 0.7 screw
Hook
Outline
Leakage
dimension
current
Mass
(mA) ∗2
(Unit: mm)
(kg)
(reference
H
D
value)
200
36.5
0.7
10
210
46
1.2
44.5
210
47
2
68.4
168
47
0.7
9.5
Outline dimension
Leakage
(Unit: mm)
current
Mass
(mA) ∗2
(kg)
(reference
W
H
D
D1
value)
253 530 60
35 4.7
76
15
10
(Unit: mm)
Loss
(W)
7.3
8
15
11
W
Loss
(W)
56
W
D1
10
D
D
29