Mitsubishi Electric FREQROL-CS80 Manual page 22

Hide thumbs Also See for FREQROL-CS80:
Table of Contents

Advertisement

Function
Pr.
44
F020
45
F021
57
A702
58
A703
59
F101
60
G030
65
H300
66
H611
67
H301
68
H302
69
H303
71
C100
72
E600
73
T000
74
T002
E100
75
E101
E102
77
E400
78
D020
79
D000
8
80
C101
82
C125
90
C120
96
C110
100
G040
101
G041
102
G042
103
G043
104
G044
105
G045
117
N020
118
N021
119
N022
N023
120
N024
121
N025
122
N026
123
N027
124
N028
125
T022
126
T042
127
A612
128
A610
129
A613
130
A614
131
A601
132
A602
133
A611
134
A615
145
E103
150
M460
151
M461
22
156
H501
157
M430
Pr.
Name
group
Second acceleration/deceleration time
Second deceleration time
Restart coasting time
Restart cushion time
Remote function selection
Energy saving control selection
Retry selection
Stall prevention operation reduction starting
frequency
Number of retries at fault occurrence
Retry waiting time
Retry count display erase
Applied motor
PWM frequency selection
Analog input selection
Input filter time constant
Reset selection/disconnected PU detection/
PU stop selection
Reset selection
Disconnected PU detection
PU stop selection
Parameter write selection
Reverse rotation prevention selection
Operation mode selection
Motor capacity
Motor excitation current
Motor constant (R1)
Auto tuning setting/status
V/F1 (first frequency)
V/F1 (first frequency voltage)
V/F2 (second frequency)
V/F2 (second frequency voltage)
V/F3 (third frequency)
V/F3 (third frequency voltage)
PU communication station number
PU communication speed
PU communication stop bit length / data
length
PU communication data length
PU communication stop bit length
PU communication parity check
PU communication retry count
PU communication check time interval
PU communication waiting time setting
PU communication CR/LF selection
Terminal 2 frequency setting gain frequency
Terminal 4 frequency setting gain frequency
PID control automatic switchover frequency
PID action selection
PID proportional band
PID integral time
PID upper limit
PID lower limit
PID action set point
PID differential time
PU display language selection
Output current detection level
Output current detection signal delay time
Stall prevention operation selection
OL signal output timer
Minimum
Setting range
setting
increment
0 to 3600 s
0.1 s
0 to 3600 s, 9999
0.1 s
0, 0.1 to 5 s, 9999
0.1 s
0 to 60 s
0.1 s
0 to 3
1
0, 9
1
0 to 5
1
0 to 400 Hz
0.01 Hz
0 to 10, 101 to 110
1
0.1 to 600 s
0.1 s
0
1
0 to 2
1
2 to 12
1
0, 1, 10, 11
1
0 to 8
1
0 to 3, 14 to 17
1
0, 1
0 to 2
1
0 to 2
1
0 to 4
1
0.2 to 15 kW, 9999
0.01 kW
0 to 500 A, 9999
0.01 A
0 to 50 Ω, 9999
0.001 Ω
0, 1
1
0 to 400 Hz, 9999
0.01 Hz
0 to 1000 V
0.1 V
0 to 400 Hz, 9999
0.01 Hz
0 to 1000 V
0.1 V
0 to 400 Hz, 9999
0.01 Hz
0 to 1000 V
0.1 V
0 to 31(0 to 247)
1
48, 96, 192, 384, 576,
1
768, 1152
0, 1, 10, 11
1
0, 1
0, 1
0 to 2
1
0 to 10, 9999
1
0, 0.1 to 999.8 s, 9999
0.1 s
0 to 150 ms, 9999
1 ms
0 to 2
1
0 to 400 Hz
0.01 Hz
0 to 400 Hz
0.01 Hz
0 to 400 Hz, 9999
0.01 Hz
0, 20, 21
1
0.1 to 1000%, 9999
0.1%
0.1 to 3600 s, 9999
0.1 s
0 to 100%, 9999
0.1%
0 to 100%, 9999
0.1%
0 to 100%, 9999
0.01%
0.01 to 10 s, 9999
0.01 s
0 to 7
1
0 to 200%
0.1%
0 to 10 s
0.1 s
0 to 31, 100, 101
1
0 to 25 s, 9999
0.1 s
Initial
Customer
value
setting
5 s
∗2
10 s
∗2
15 s
∗2
9999
9999
1 s
0
0
0
50 Hz
0
1 s
0
0
2
1
1
14
0
1
2
0
0
9999
9999
9999
0
9999
0 V
9999
0 V
9999
0 V
0
192
1
0
1
2
1
0
9999
1
50 Hz
50 Hz
9999
0
100%
1 s
9999
9999
9999
9999
1
150%
0 s
0
0 s