Delay Profile - York F*FP Technical Manual

Single piece air handlers for use with split-system cooling & heat pumps
Table of Contents

Advertisement

EXTENDED AIR FLOW DATA - F4FV VARIABLE SPEED MODELS
CFM/TAP SELECTION - F4FV
High Speed
Cooling and
Model
Jumper
F4FV060H06T2*
"COOL" TAP
2100
1980
1860
1750
1675
1605
1575
1510
1420
1335
1280
1200
NOTE:
1. Both the "COOL" and the "ADJ" tap must be set for the cooling CFM.
2. Fan only CFM = 63% of high speed cooling.
3. Low speed cooling used only with two stage outdoor units.
(Speed is preset to 65% of high speed).
4. Dehumidification speed is 85% of cooling speed.
5. When operating in both heat pump and electric heat modes, the CFM will
be whichever is greater.
6. CFM indicator light flashes once for every 100 CFM (i.e., 12 Flashes is
1200 CFM).
ELECTRIC HEAT CFM
Model
F4FV060H06T2*
6
1
Heat Pump CFM
Setting
"ADJ TAP"
"A"
"B"
"B"
"B"
"A"
"A"
"B"
"A"
"A"
"C"
"C"
"B"
"B"
"C"
"D"
"B"
"C"
"A"
"D"
"A"
"C"
"C"
"D"
"C"
CFM
Tap Selections
"HEAT"
1860
"A"
1750
"B"
1420
"C"
1335
"D"

DELAY PROFILE

"DELAY" Tap
A
B
C
D
Normal
The normal setting provides a 30-second ramp-up from zero
airflow to full capacity and a 30-second ramp-down from full
capacity back to zero airflow. Whenever there is a change in
airflow mode, such as a call for cooling or a change from low
heat to high heat, the motor will take 30 seconds to ramp
from one speed to the other.
Humid
The humid setting is best-suited for installations where the
humidity is frequently very high during cooling season, such
as in the southern part of the country. On a call for cooling,
the blower will ramp up to 50% of full capacity and will stay
there for two minutes, then will ramp up to 82% of full capac-
ity and will stay there for five minutes, and then will ramp up
to full capacity, where it will stay until the wall thermostat is
satisfied. In every case, it will take the motor 30 seconds to
ramp from one speed to another.
Dry
The dry setting is best suited to parts of the country where
excessive humidity is not generally a problem, where the
summer months are usually dry. On a call for cooling the
motor will ramp up to full capacity and will stay there until the
thermostat is satisfied. At the end of the cooling cycle, the
blower will ramp down to 50% of full capacity where it will stay
for 60 seconds. Then it will ramp down to zero. In every case,
it will take the motor 30 seconds to ramp from one speed to
another.
Temperate
The temperate setting is best suited for most of the country,
where neither excessive humidity nor extremely dry condi-
tions are the norm. On a call for cooling, the motor will ramp
up to 63% of full capacity and will stay there for 90 seconds,
then will ramp up to full capacity. At the end of the cooling
cycle, the motor will ramp down to 63% of full capacity and
will stay there for 30 seconds, then will ramp down to zero. In
every case, it will take the motor 30 seconds to ramp from
one speed to another.
295421-YTG-B-0707
Comfort Setting
Normal
Humid
Dry
Temperate
Unitary Products Group