Power Wiring Field Diagram; Electrical Data - York DNP024 Technical Manual

Affinity series single package gas/electric air cooled air conditioners 2 thru 5 nominal ton
Hide thumbs Also See for DNP024:
Table of Contents

Advertisement

036-21366-007-A-1205
FIGURE 4 - POWER WIRING FIELD DIAGRAM
TABLE 14: ELECTRICAL DATA
LIMITATIONS
MODEL
POWER SUPPLY
DNP
MIN.
024
208/230-1-60
030
208/230-1-60
030
208/230-3-60
030
460-3-60
036
208/230-1-60
036
208/230-3-60
036
460-3-60
036
575-3-60
042
208/230-1-60
042
208/230-3-60
042
460-3-60
042
575-3-60
048
208/230-1-60
048
208/230-3-60
048
460-3-60
048
575-3-60
060
208/230-1-60
060
208/230-3-60
060
460-3-60
060
575-3-60
1.
Rated in accordance with ARI Standard 110, utilization range "A".
2.
Dual element, time delay type.
Unitary Products Group
VOLTAGE
COMPRESSOR
1
MAX.
RLA
LRA
187
253
8.0
53.5
187
253
13.6
67
187
253
8.6
55
432
504
5.7
39
187
253
17.2
88
187
253
11.4
77
432
504
5.7
39
540
630
4.7
31
187
253
20
104
187
253
13.9
88
432
504
6.4
44
540
630
5.4
34
187
253
23.4
126
187
253
13
93
432
504
6.4
46.5
540
630
5.1
37.2
187
253
25
150
187
253
17.3
123
432
504
8.4
70
540
630
7.0
53
SUPPLY
COND.
AIR
MINIMUM
FAN
BLOWER
CIRCUIT
MOTOR,
MOTOR
AMPACITY
FLA
FLA
1.1
2.6
16.5
1.1
6.8
24.9
1.1
6.8
18.7
0.6
6.8
13.4
1.1
6.8
29.4
1.1
6.8
22.2
0.6
6.8
14.8
0.6
6.8
13.3
1.3
9.1
35.4
1.3
9.1
27.8
0.7
9.1
18.5
0.6
9.1
16.8
1.9
9.1
39.5
1.9
9.1
26.5
1.0
9.1
18.4
0.8
9.1
17.3
2.8
9.1
43.2
2.8
9.1
33.5
2.8
9.1
22.6
2.8
9.1
21.2
MAX.
MAX.
HACR
UNIT
FUSE
BREAKER
POWER
SIZE,
SIZE,
FACTOR
2
AMPS
AMPS
20
20
0.96
35
35
0.96
25
25
0.96
20
20
0.96
45
45
0.96
30
30
0.96
20
20
0.96
20
20
0.96
50
50
0.96
40
40
0.96
25
25
0.96
25
25
0.96
60
60
0.96
35
35
0.96
25
25
0.96
25
25
0.96
60
60
0.96
45
45
0.96
30
30
0.96
30
30
0.96
TRANSFORMER
SIZE (VA)
40
40
75
75
40
75
75
75
40
75
75
75
40
75
75
75
40
75
75
75
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dnp060Dnp030Dnp036Dnp042Dnp048

Table of Contents