TABLE 15: DF PHYSICAL DATA
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
TABLE 16: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
208
240
480
600
14
MODELS
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP (Direct Drive)
Fan Motor HP (Belt Drive)
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Propeller Dia. (in.)
Fan Motor Hp
Nom. CFM
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Recip Type
Quantity Per Unit (15" X 20" X 1" or 2")
Quantity Per Unit (14" X 25" X 1" or 2")
Total Face Area (sq. ft.)
Refrigerant 22
(lbs./oz.)
kW CAP. MULTIPLIER
208
0.75
230
0.92
460
0.92
575
0.92
DF
072
12 X 10
1
1 1/2
4
13
5.1
24
1/2
4200
2
18
17.1
1
2
1
6.3
11/10
TABLE 17: VOLTAGE LIMITATIONS
POWER SUPPLY
208/230-3-60
460-3-60
575-3-60
1. Utilization Range "A" in accordance with ARI Standard
110.
254599-YTG-C-0807
1
VOLTAGE
MIN.
MAX.
187
252
432
504
540
630