Natural Gas Pipe Sizing Chart; Propane (Lp) Gas Pipe Sizing Chart; Flue Vent Hood; Flue Vent Outlet Air Hood - York AFFINITY SERIES R-410A Installation Manual

R-410a affinity series 2-4 ton
Hide thumbs Also See for AFFINITY SERIES R-410A:
Table of Contents

Advertisement

Table 7: Natural Gas Pipe Sizing Chart
Nominal Inches Iron Pipe Size
Length
In Feet
1/2"
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
43
90
40
100
38
1. Maximum capacity of pipe in cubic feet of gas per hour
(based upon a pressure drop of 0.3 inch water column and
0.6 specific gravity gas).
Table 8: Propane (LP) Gas Pipe Sizing Chart
Length
Nominal Inches Iron Pipe Size
In Feet
1/2"
10
275
20
189
30
152
40
129
50
114
60
103
70
96
80
89
90
83
100
78
1. Maximum capacity of pipe in thousands of BTU per hour
(based upon a pressure drop of 0.5 inch water column).
If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel pipe
must be installed at the gas valve and extend a
minimum of two (2) inches outside of the unit casing.
Natural gas may contain some propane. Propane being
an excellent solvent, will quickly dissolve white lead or
most standard commercial compounds. Therefore, a
special pipe dope must be applied when wrought iron or
steel pipe is used. Shellac base compounds such as
gaskoloc or stalastic, and compounds such as
rectorseal # 5, Clyde's or John Crane may be used.
4.
All piping should be cleaned of dirt and scale by
hammering on the outside of the pipe and blowing out the
loose dirt and scale. Before initial start-up, be sure that all
of the gas lines external to the unit have been purged of air.
5.
The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
16
1
3/4"
1"
1-1/4"
278
520
1,050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
1
3/4"
1"
1-1/4"
567
1,071
2,205
393
732
1,496
315
590
1,212
267
504
1,039
237
448
913
217
409
834
196
378
771
185
346
724
173
322
677
162
307
630
Limitations, shown on Page 3. After the gas connections
have been completed, open the main shut-off valve
admitting normal gas pressure to the mains. Check all
joints for leaks with soap solution or other material suitable
for the purpose. NEVER USE A FLAME.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury or loss of life.
6.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
before conducting any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2
psig (3.48 kPa).

Flue Vent Hood

The flue vent hood with screen is shipped loose. This hood must
be installed to assure proper unit operation. The hood must be
fastened to the outside of the side gas control/electrical
compartment with the screws provided in the bag attached to the
inside of the gas control/electrical compartment, see Figure 13.
Flue hood surfaces may be hot.
Figure 13: Flue Vent Outlet Air Hood
The flue exhaust hood must be properly installed and
within the recommended clearances. Further commu-
nications and action must be given to the home or
building owner(s) to eliminate any unauthorized human
contact around this area during the heating cycle. Flue
hood surface and the immediate area reach high tem-
peratures during the heating cycle.
279550-YIM-A-0207
Unitary Products Group

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dnx024Dnx036Dnx048

Table of Contents