Shut-Off; Natural Gas Pipe Sizing Chart; Propane (Lp) Gas Pipe Sizing Chart - York DNH018 Installation Manual

Champion plus single packaged gas/electric air cooled air conditioners 1-1/2 through 5 nominal ton
Hide thumbs Also See for DNH018:
Table of Contents

Advertisement

.
1 / 2 x 1 / 2 U N I O N
1 / 2 x 1 / 2 G A S C O C K
D R I P L E G
FIGURE 5 -
EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
TABLE 5: NATURAL GAS PIPE SIZING CHART
NOMINAL INCHES IRON PIPE SIZE
LENGTH
IN FEET
1/2"
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
43
90
40
100
38
1.
Maximum capacity of pipe in cubic feet of gas per hour (based
upon a pressure drop of 0.3 inch water column and 0.6 specific
gravity gas).
10
A U T O M A T I C
G A S V A L V E
1 / 2 - 1 4 N P T
3/4"
1"
1-1/4"
278
520
1,050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
TABLE 6: PROPANE (LP) GAS PIPE SIZING
CHART
LENGTH
IN FEET
10
20
30
40
50
60
70
80
1
90
100
1.
Maximum capacity of pipe in thousands of BTU per hour (based
upon a pressure drop of 0.5 inch water column).
If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel
pipe must be installed at the gas valve and extend
a minimum of two (2) inches outside of the unit
casing.
i
Natural gas may contain some propane. Propane
being a excellent solvent, will quickly dissolve
white lead or most standard commercial com-
pounds. Therefore, a special pipe dope must be
applied when wrought iron or steel pipe is used.
Shellac base compounds such as gaskoloc or sta-
lastic, and compounds such as rectorseal # 5,
Clyde's or John Crane may be used.
66324-YIM-B-1004
1
NOMINAL INCHES IRON PIPE SIZE
1/2"
3/4"
1"
275
567
1,071
189
393
732
152
315
590
129
267
504
114
237
448
103
217
409
96
196
378
89
185
346
83
173
322
78
162
307
Unitary Products Group
1-1/4"
2,205
1,496
1,212
1,039
913
834
771
724
677
630

Hide quick links:

Advertisement

Table of Contents