Characteristics; Specifications - Delta RTU-ECAT Operation Manual

Ethercat remote io communication module
Table of Contents

Advertisement

RTU-ECAT Operation Manual
1. Thank you for choosing Delta RTU-ECAT. To ensure correct installation and operation of RTU-ECAT,
please read this manual carefully before use.
2. This manual only provides introductory information on RTU-ECAT. For more detailed information on
EtherCAT protocol, please refer to relevant references or literatures.
3. RTU-ECAT is defined as an EtherCAT slave and DVP-S series DI/DO modules and special modules can
be connected on its right side.
_2
4. Refer to DVP-PLC Application Manual: Special Modules for more details on how to use DVP-S series
special modules.
2.1

Characteristics

Compliant with the EtherCAT protocol, RTU-ECAT supports PDO, SDO and other services in the COE
protocol.
Supports Distributed Clock SYNC and SyncManagers SYNC.
On its right side, RTU-ECAT connects DVP-S series right-side modules with maximum 128 digital input
points and 128 digital output points as well as maximum 8 special modules such as analog modules,
temperature modules, pulse modules and etc.
Maximum 14 DVP-S series digital modules and special modules in total can be connected to the right
side of RTU-ECAT.
Users can select that the output values of right-side special modules and digital output point values of
digital modules keep the same as they are before disconnection or change to zero when RTU-EtherCAT
is disconnected from the master.
2.2

Specifications

Electrical specification
Item
Power voltage
Consumption power
Isolation voltage
EtherCAT specification
Item
Communication protocol
Supported service
Physical layer
Baud rate
Transmission medium
Transmission distance
Topology Structure
2-2
Specification
24 VDC (-15% ~ 20%)
1.8 W
500 V
Specification
EtherCAT Protocol
CoE(PDO, SDO)
100BASE-TX
100Mbps
Cat 5 or above shielded cable
100m
Linear topology