Current Output; Digital Output - Pulse - Siemens SITRANS FM MAG 5000 Operating Instructions Manual

Electromagnetic flowmeters ip67
Hide thumbs Also See for SITRANS FM MAG 5000:
Table of Contents

Advertisement

B.3

Current output

Current output
1)
2)
3)
B.4

Digital output - pulse

SITRANS FM MAG 5000/6000 IP67
Operating Instructions, 12/2019, A5E02338368-AD
Current output
Off
On
Off
Current output
Current output
Time const.
If HART communication is installed, it is not possible to set the output for 0-20 mA (even though
the option is visible in the display). This is due to the fact that HART does not work if the output
falls below 2-3 mA.
4-20 mA + Alarm is the default setting for MAG 6000 I. For all other variants, the default setting
is 4-20 mA.
For MAG 6000 I only: The controlling of alarm levels does not recognize if the jumper is mounted
for passive output. Do not combine differentiation and low alarm level together with passive
output. The output will try to pull down the level to 1.3 mA at fatal errors which is not possible for
passive output.
Current output
Unidirectional
Unidirectional
Bidirectional
Alarm
Current output
Alarm level: Low
Alarm
Low
High
Menu diagrams
B.4 Digital output - pulse
Current output
Alarm diff: No
No
Yes