4 Mode of Operation
4.3 FB "LHcs4x00_Control"
4.3.1

Program workflow

Figure 4-3
no
PN
When first executing the FB "LHcs4x00_Control", possibly existing diagnostic
entries are deleted by means of FC "LHcs4x00_Diag86" (see chapter 4.5).
The communication type (PROFINET or PROFIBUS) is detected via the hardware
ID of the HCS.
Subsequently, the input and output address areas of the configured HCS, including
modules (CIM, PM and POM), are read out.
HCS4x00Library
Entry ID: 109478117,
V2.2.1,
Start/Stop
firstRun?
yes
Delete diag buffer
PN or DP ?
DP
get I/O addresses
read I/O from
periphery
write I/O to
periphery
write datasets
(dsNum)
read datasets
(dsNum)
search for
errors
09/2018
FC "LHcs4x00_Diag86"
config.hcs[x].ioDataIn.hwIoDevice
CIM
PM
POMs
status bits
voltage
PM inputs
power output actual value
control bits
PM outputs
power output setpoints
ds100: field type 1
ds150: production field values
ds151: standby field values
ds152: channels without diagnostic alarm
ds160: control of internal fans
ds190: reset HCS
ds002: configuration data for POM4220 Highend
ds101..ds132: field type 2
ds100: field type 1
ds150: production field values
ds151: standby field values
ds152: channels without diagnostic alarm
ds160: control of internal fans
ds200: measured values
ds201: versions
ds202: measured values of PM4000 U/I
ds002: configuration data of POM4220 Highend
ds203: measured values of POM4220 Highend
ds101..ds132: field type 2
general fault (CIM)
general fault (POM)
channel fault (POM)