Service Settings - Trane ADAPTIVE CONTROL UCM-CLD Installation Operation & Maintenance

Operating and control principles
Table of Contents

Advertisement

Service settings

* If the keypad is locked and a diagnostic occurs,
the alarm light will flash if applicable but the
diagnostic screen will not be displayed until the
keypad is unlocked.
** Once the keypad is locked the "PREVIOUS" and
"ENTER" key need to be pressed simultaneously
to unlock the keypad.
Default = Disable
The optional under/over voltage transformer is
needed for this feature.
Default = 460
Selections = 200, 220, 230, 346, 380, 415, 460, 500,
575.
Default = 120 seconds
select = 30 to 120 seconds
The time period between power-up or stop and the
initiation of the compressor start sequence, when
there is a call for cooling.
Default = Disable
[UNITS]
SI
English
[LANGUAGE]
English / Français / Espanol / Nippon / Italiano /
Deutsch / Nederlands
Default = 1
Select = 1 to 12
Default = Disable
Service
Service settings, enable and units
settings
"Press (Next) (Previous) to continue"
Status of keypad/display lock feature
Enable
"Press (Enter) to lock display and keypad"
password will be required to unlock
Depress either Enter or Next
*
***DISPLAY AND KEYPAD ARE LOCKED ***
*** ENTER PASSWORD TO UNLOCK ***
"Chiller operating mode"
Under/Over voltage protection
"Press (+) (-) to change setting"
Unit line voltage
"Press (+) (-) to change setting"
Restart inhibit time
"Press (+) (-) to change setting"
Balanced compressor start and hours
"Press (+) (-) to change setting"
Display units
"Press (+) (-) to change setting"
Language
"Press (+) (-) to change setting"
** Programmable relay setup
"Press (+) (-) to change setting"
External circuit lockout
"Press (+) (-) to change setting"
*** Password required for further access
13
Next
(Service setting menu)
Disable
Next
Enter
** Previous
Enter
Display will return to
under chiller report
[Disable/Enable]
Next
Next
Next
[Disable/Enable]
Next
Next
[LANGUAGE]
Next
Next
[Disable/Enable]
Next
"Please enter password"
Next
Next
[VOLT] V
XXX SEC
[UNITS]
XX

Hide quick links:

Advertisement

Table of Contents
loading