8. Cooling capacity table
• For cooling operation optional parts of Cooling kit is necessary.
• FT: Flow temperature
• OT: Outdoor temperature
• CC: Cooling capacity (kW)
• IP: Input power (kW)
• COP: Coefficient Of Performance
• Usage environment, such as operation of the heating equipment, room temperature, and control
adjustments may cause disparities between practically determined and measured values.
8-1. Model: WOYG160LJL
FT
7°C
OT
CC
IP
COP
20°C
9.96
3.49
2.85
25°C
9.89
3.95
2.50
30°C
9.20
4.15
2.22
35°C
8.50
4.34
1.96
40°C
8.05
4.70
1.71
46°C
7.00
4.70
1.49
NOTE: The values of heating capacity/input power/COP are based on measurement of EN14511 standard:
• FT < 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 7°C / 12°C, 1,464 l/h
• FT ≥ 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 18°C / 23°C, 2,416 l/h
8-2. Model: WOYK150LJL
FT
7°C
OT
CC
IP
COP
20°C
9.61
3.30
2.91
25°C
9.51
3.71
2.56
30°C
9.01
3.91
2.30
35°C
8.50
4.11
2.07
40°C
7.96
4.57
1.74
46°C
7.10
4.84
1.47
NOTE: The values of heating capacity/input power/COP are based on measurement of EN14511 standard:
• FT < 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 7°C / 12°C, 1,464 l/h
• FT ≥ 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 18°C / 23°C, 2,416 l/h
8-3. Model: WOYK170LJL
FT
7°C
OT
CC
IP
COP
20°C
10.17
3.52
2.89
25°C
10.07
3.96
2.54
30°C
9.54
4.18
2.28
35°C
9.00
4.39
2.05
40°C
8.43
4.88
1.73
46°C
7.52
5.17
1.45
NOTE: The values of heating capacity/input power/COP are based on measurement of EN14511 standard:
• FT < 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 7°C / 12°C, 1,550 l/h
• FT ≥ 10°C: The flow rate obtained during the test at the standard rating conditions of OT 35°C and Water temp. flow/return 18°C / 23°C, 2,503 l/h
8-1. Model: WOYG160LJL
10°C
13°C
CC
IP
COP
CC
IP
11.95
3.84
3.11
13.82
4.12
11.84
4.23
2.80
13.65
4.45
11.08
4.51
2.46
12.82
4.79
10.31
4.78
2.16
11.98
5.12
9.16
4.72
1.94
10.27
4.74
7.92
4.73
1.67
8.84
4.74
10°C
13°C
CC
IP
COP
CC
IP
11.61
3.54
3.28
13.50
3.72
11.34
3.87
2.93
13.09
4.00
10.69
4.12
2.59
12.31
4.30
10.03
4.37
2.30
11.53
4.59
9.15
4.62
1.98
10.34
4.66
8.13
4.86
1.67
9.13
4.84
10°C
13°C
CC
IP
COP
CC
IP
12.22
3.80
3.22
14.12
4.01
11.93
4.15
2.87
13.69
4.31
11.25
4.42
2.55
12.88
4.63
10.56
4.69
2.25
12.06
4.94
9.63
4.95
1.95
10.82
5.02
8.56
5.21
1.64
9.55
5.21
- (01-18) -
15°C
COP
CC
IP
COP
CC
3.35
15.00
4.26
3.52
16.67
3.07
14.78
4.56
3.24
16.36
2.68
13.90
4.93
2.82
15.18
2.34
13.02
5.29
2.46
14.00
2.17
11.00
4.75
2.32
12.11
1.86
9.45
4.75
1.99
10.38
15°C
COP
CC
IP
COP
CC
3.63
14.68
3.82
3.84
16.37
3.27
14.21
4.07
3.49
15.84
2.86
13.37
4.39
3.05
14.93
2.51
12.52
4.71
2.66
14.00
2.22
11.15
4.70
2.37
12.38
1.89
9.78
4.81
2.03
10.73
15°C
COP
CC
IP
COP
CC
3.52
15.30
4.12
3.71
16.95
3.18
14.81
4.39
3.37
16.41
2.78
13.93
4.74
2.94
15.46
2.44
13.04
5.08
2.57
14.50
2.16
11.62
5.07
2.29
12.82
1.83
10.19
5.19
1.96
11.11
18°C
22°C
IP
COP
CC
IP
COP
4.41
3.78
18.70
4.48
4.17
4.68
3.50
18.26
4.75
3.84
4.92
3.09
17.21
5.13
3.35
5.15
2.72
16.16
5.50
2.94
4.77
2.54
13.59
4.80
2.83
4.75
2.19
11.62
4.74
2.45
18°C
22°C
IP
COP
CC
IP
COP
3.90
4.20
18.41
3.94
4.67
4.13
3.84
17.89
4.18
4.28
4.40
3.39
16.87
4.56
3.70
4.66
3.00
15.83
4.94
3.20
4.74
2.61
14.02
4.80
2.92
4.74
2.26
11.94
4.60
2.60
18°C
22°C
IP
COP
CC
IP
COP
4.23
4.01
18.92
4.29
4.41
4.48
3.66
18.38
4.55
4.04
4.77
3.24
17.33
4.97
3.49
5.05
2.87
16.27
5.38
3.02
5.14
2.49
14.41
5.23
2.76
5.14
2.16
12.27
5.01
2.45
8. Cooling capacity table