Registers 00044 To 00048: Internal Commands - Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection; motor protection; voltage and frequency protection;
Hide thumbs Also See for SIPROTEC 7SJ80:
Table of Contents

Advertisement

Register Designation of the SIPROTEC objects
00039
<user-defined>
00040
<user-defined>
00041
<user-defined>
00042
<user-defined>
00043
<user-defined>
1.3.3

Registers 00044 to 00048: Internal commands

Register Designation of the SIPROTEC objects
Command: ModeREMOTE
00044
Indication: ModeREMOTE
Command: Group A
00045
Indication: Group A
Command: Group B
00046
Indication: Group B
Command: Group C
00047
Indication: Group C
Command: Group D
00048
Indication: Group D
SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2240-A320-3
Comment
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
Comment
Control mode REMOTE
0 = Set to LOCKED
1 = Set to UNLOCKED
Control mode REMOTE
0 = LOCKED
1 = UNLOCKED
0 = not allowed
1 = Activation of setting group A
0 = Setting group A not active
1 = Setting group A is active
0 = not allowed
1 = Activation of setting group B
0 = Setting group B not active
1 = Setting group B is active
0 = not allowed
1 = Activation of setting group C
0 = Setting group C not active
1 = Setting group C is active
0 = not allowed
1 = Activation of setting group D
0 = Setting group D not active
1 = Setting group D is active
Modbus Register Map Organization