Registers 40301 To 40324: Statistic Values - Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection; motor protection; voltage and frequency protection;
Hide thumbs Also See for SIPROTEC 7SJ80:
Table of Contents

Advertisement

1.6.5

Registers 40301 to 40324: Statistic values

Designation of the
Register
SIPROTEC objects
40301
-
Ia =
40302
40303
-
Ib =
40304
40305
-
Ic =
40306
40307
-
<user-defined>
40308
40309
-
<user-defined>
40310
40311
-
Sum Ia =
40312
40313
-
Sum Ib =
40314
40315
-
Sum Ic =
40316
40317
-
Op.Hours =
40318
SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2240-A320-3
• Registers are write-protected.
• Statistic values can be routed on these positions as a "Destination system interface"
using the DIGSI Configuration matrix.
Primary fault current Ia
Primary fault current Ib
Primary fault current Ic
not pre-allocated
not pre-allocated
Accumulation of interrupted current
Ph A
Accumulation of interrupted current
Ph B
Accumulation of interrupted current
Ph C
Counter of operating hours
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
Modbus Register Map Organization
1
Comment
Scaling
(100000 corresponds
to ...)
1000.00 kA
1000.00 kA
1000.00 kA
-
-
1000.00 kA
1000.00 kA
1000.00 kA
100000 hours
Internal
object
no.
533
534
534
-
-
1021
1022
1023
1020
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents