Control Relay Output Blocks/Binary Output Status; Internal Commands; User-Allocated Single Commands - Siemens SIPROTEC 7SD80 Manual

Line differential protection communication module dnp 3.0 buss mapping / point list
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

3 Point lists

3.2 Control Relay Output Blocks/Binary Output Status

3.2
Control Relay Output Blocks/Binary Output Status
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate),
Point
Name
Index
3.2.1

Internal commands

79 ON
8
ProtActive
9
Group A
10
Group B
11
Group C
12
Group D
13
Test 87
14
Commiss. 87
15
ModeREMOTE
17
3.2.2

User-allocated single commands

Please ref. to chap. 1.2.1 for additional notes.
*
<unnamed>
18
<unnamed>
19
<unnamed>
20
<unnamed>
21
<unnamed>
22
<unnamed>
23
<unnamed>
24
<unnamed>
25
<unnamed>
26
<unnamed>
27
* The names are defined during indication allocation using parametrization software DIGSI 4
26
6 (direct operate, no ack)
Description
Activation / deactivation of Auto-reclosure function
Protection activation / deactivation
Select setting group A and deactivate setting group
B,C,D (ref. to chap. 1.2.3)
Select setting group B and deactivate setting group
A,C,D
Select setting group C and deactivate setting group
A,B,D
Select setting group D and deactivate setting group
A,B,C
87 Set test state of 87; ON=1, OFF=0
87 Set commissioning state of 87; ON=1, OFF=0
Mode remote control; UNLOCKED=1, LOCKED=0
(ref. to chap. 1.2.2)
User output 1
User output 2
User output 3
User output 4
User output 5
User output 6
User output 7
User output 8
User output 9
User output 10
Supported Control
Relay Output Block
Fields
Latch On, Latch Off
Latch On, Latch Off
Latch On
Latch On
Latch On
Latch On
Latch On; Latch Off
Latch On; Latch Off
Latch On; Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
Latch On, Latch Off
SIPROTEC, 7SD80, Bus mapping DNP 3.0
C53000-L2040-C347-1, Edition 07.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents