Device Profile Document - Siemens SIPROTEC 7SD80 Manual

Line differential protection communication module dnp 3.0 buss mapping / point list
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

DNP V3.0 Device Profile

2.2 Device Profile Document

2.2
Device Profile Document
DNP V3.0
DEVICE PROFILE DOCUMENT
SIEMENS AG
Vendor Name:
Device Name: 7SD80
Highest DNP Level Supported:
For Requests
DNP-L2
For Responses
DNP-L2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08
(limited quantity), and 17 and 28 (index) are supported in addition to request qualifier code 06 (no range).
Static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01.
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-
event object requests, qualifiers 17 or 28 are always responded.
16-bit Analog Change Events with Time may be requested.
The write function code for Object 50 (Time and Date), variation 1, is supported.
The features outlined within this Device Profile have successfully passed DNP Conformance Test of Subset
Level 2 outlined in DNP3-2000 IED Certification Procedure.
Maximum Data Link Frame Size (octets):
Transmitted____292_____________
Received______292_____________
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range 0 to 255
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If 'Sometimes', when? ______________________________________
Configurable If 'Configurable', how? by the protection data processing program DIGSI 4
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes If 'Sometimes', when? ___________________________________
Configurable If 'Configurable', how? by the protection data processing program DIGSI 4
18
Device Function:
Master
Slave
Maximum Application Fragment Size (octets):
Transmitted _Configurable up to 2048
Received_______2048_______
Maximum Application Layer Re-tries:
None
Configurable, range ____ to _______
(Fixed is not permitted)
SIPROTEC, 7SD80, Bus mapping DNP 3.0
C53000-L2040-C347-1, Edition 07.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents