Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Name
Index
5X-B Pickup Ph A
80
5X-B Pickup Ph B
81
5X-B Pickup Ph C
82
5X-B Pickup Gnd
83
50(N)-B1 PICKUP
84
50(N)-B2 PICKUP
85
51(N)-B PICKUP
86
50-STUB PICKUP
87
5X-B TRIP
88
50(N)-B1 TRIP
93
50(N)-B2 TRIP
94
51(N)-B TRIP
95
50-STUB TRIP
96
3.1.5

Thermal overload protection

49 O / L OFF
97
49 O/L BLOCK
98
49 O/L ACTIVE
99
49 O/L I Alarm
100
49 O/L Θ Alarm
101
49 Winding O/L
102
49 Th O/L TRIP
103
3.1.6

Circuit breaker test

CB1-TESTtripABC
107
CB1-TEST close
108
CB-TEST running
109
3.1.7

Measurement supervision

Fail I Superv.
110
Fail I balance
111
Fail V Superv.
112
Fail V balance
113
MeasSup OFF
114
Broken Iwire L1
116
Broken Iwire L2
117
Broken Iwire L3
118
3.1.8

Diagnosis / General alarms

Device OK
119
SIPROTEC, 7SD80, Bus mapping DNP 3.0
C53000-L2040-C347-1, Edition 07.2011
Description
50(N)/51(N) Backup O/C PICKUP Phase A; ON=1, OFF=0
50(N)/51(N) Backup O/C PICKUP Phase B; ON=1, OFF=0
50(N)/51(N) Backup O/C PICKUP Phase C; ON=1, OFF=0
50(N)/51(N) Backup O/C PICKUP GROUND; ON=1, OFF=0
50(N)-B1 Pickup; ON=1, OFF=0
50(N)-B2 Pickup; ON=1, OFF=0
51(N)-B Pickup; ON=1, OFF=0
50-STUB Pickup; ON=1, OFF=0
50(N)/51(N)-B General TRIP command; ON=1, OFF=0
50(N)-B1 TRIP command; ON=1, OFF=0
50(N)-B2 TRIP command; ON=1, OFF=0
51(N)-B TRIP command; ON=1, OFF=0
50-STUB General TRIP command; ON=1, OFF=0
49 Overload Protection is OFF; ON=1, OFF=0
49 Overload Protection is BLOCKED; ON=1, OFF=0
49 Overload Protection is ACTIVE; ON=1, OFF=0
49 Overload Current Alarm (I alarm) ; ON=1, OFF=0
49 Overload Alarm! Near Thermal Trip; ON=1, OFF=0
49 Winding Overload; ON=1, OFF=0
49 Thermal Overload TRIP; ON=1, OFF=0
CB1-TEST TRIP command ABC; ON=1, OFF=0
CB1-TEST CLOSE command; ON=1, OFF=0
CB-TEST is in progress; ON=1, OFF=0
Failure: general Current Supervision; ON=1, OFF=0
Failure: Current Balance; ON=1, OFF=0
Failure: general Voltage Supervision; ON=1, OFF=0
Failure: Voltage Balance; ON=1, OFF=0
Measurement Supervision is switched OFF; ON=1, OFF=0
Alarm: Broken current-wire detected L1; ON=1, OFF=0
Alarm: Broken current-wire detected L2; ON=1, OFF=0
Alarm: Broken current-wire detected L3; ON=1, OFF=0
Device is operational and protecting; ON=1, OFF=0
3 Point lists
3.1 Binary Input Points
Class
3
3
3
3
3
3
3
3
2
2
2
2
2
3
3
3
1
1
3
2
3
3
3
3
1
1
1
3
3
1
3
1
23