Suction Pipe Temperature Thermistor Anomaly (Tho-S); Under-Dome Temperature Thermistor Anomaly (Tho-C) - Mitsubishi Heavy Industries KXZ Series Service Manual

Vrf inverter multi-system, outdoor units
Hide thumbs Also See for KXZ Series:
Table of Contents

Advertisement

Error code
E53/E55*1
Remote control:
E53/E55
E53/E55
7-segment display: –
*1 E53 : Tho-S, E55 : Tho-C
1. Applicable model
Outdoor unit
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-S or Tho-C
3. Condition of error displayed
• If -50°C or lower is detected
for 5 seconds continuously
within 2 minutes to 2 minutes
20 seconds after compressor
ON, compressor stops. When
the compressor is restarted
automatically after 3-minutes
delay, if this anomaly occurs 3
times within 40 minutes.
4. Presumable cause
• Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of thermistor
harness connection
(connector)
• Outdoor control PCB
anomaly
Note:
LED
Green
Red
Keeps flashing Stays OFF
Indoor
Keeps flashing 1-time flash
Outdoor
5. Troubleshooting
Diagnosis
Save data for 30 minutes before stopping in Mente PC.
Is
the connector of
thermistor connected
properly ?
YES
Regarding the characteristics of
the thermistor, see the following chart.
Are
the characteristics
of thermistor OK?
※1
※1 Check several times to prove any poor connection.
Temperature-resistance characteristics of
suction pipe temperature thermistor (Tho-S)
5kΩ at 25 (ºC)
Temperature (ºC)
110
-
Content

Suction pipe temperature thermistor anomaly (Tho-S),

Under-dome temperature thermistor anomaly (Tho-C)

NO
NO
YES
Temperature-resistance characteristics of
under-dome temperature thermistor (Tho-C)
200
180
160
140
120
100
80
60
40
20
0
0
20
40
-
'14 • KX-SM-221
Countermeasure
Check and save the data of
operating conditions.
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector
securely.
Replace thermistor.
(Tho-S or Tho-C)
Replace outdoor control
PCB.
60
80
100
120
140
160
Temperature (ºC)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kxzp seriesFdc224kxzpe1Fdc280kxzpe1