Error code
E53/E55
Remote controller:
E53/E55-1
7-segment display:
E53: Tho-S, E55-1: Tho-C1
1. Applicable model
Outdoor unit
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-S or Tho-C
3. Condition of error displayed
• if -50°C or lower is detected
for 5 seconds continuously
within 2 minutes to 2 minutes
20 seconds after compressor
ON, compressor stops. When
the compressor is restarted
automatically after 3-minutes
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
• Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of thermistor
harness connection
(connector)
• Outdoor control PCB
anomaly
Note:
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing 1 time flash
Outdoor
5. Troubleshooting
Diagnosis
Save data for 30 minutes before stopping in Mente PC
Is
the connector of
thermistor connected
properly ?
YES
Regarding the characteristics of
the thermistor, see the following chart
Are
the characteristics
of thermistor OK?
*1
*1 Check several times to prove any poor connection
Temperature-resistance characreristics of
suction pipe temperature thermistor (Tho-S)
5kΩ at 25Cº
Temperature (Cº)
90
Content

Suction pipe temperature thermistor anomaly (Tho-S),

Under-dome temperature thermistor anomaly (Tho-C1)

NO
NO
YES
Temperature-resistance characreristics of
under-dome temperature thermistor (Tho-C1)
200
180
160
140
120
100
80
60
40
20
0
0
20
40
'10 • KX-SM-148
Countermeasure
Check and save the data of
operating conditions
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value
Insert the connector
securely
Replace thermistor
(Tho-S or Tho-C1)
Replace outdoor control
PCB
60
80
100
120
140
160
Temperature (Cº)