(vii) Combination of patterns which can be set for the timer operations
Sleep time
Set OFF timer by hour
Set ON timer by hour
Set OFF timer by clock
Set ON timer by clock
Weekly timer
Note (1) �: Allowed �: Not
(b) RC-E5
(i)
Sleep timer
Set the duration of time from the present to the time to turn off the air-conditioner.
It can be selected from 0 steps in the range from "OFF  hour later" to "OFF 0 hours later". After the sleep timer
setting, the remaining time is displayed with progress of time in the unit of hour.
(ii)
OFF timer
Time to turn OFF the air-conditioner can be set in the unit of 0 minutes.
(iii)
ON timer
Time to turn ON the air-conditioner can be set. Indoor temperature can be set simultaneously.
(iv)
Weekly timer
Timer operation (ON timer, OFF timer) can be set up to  times a day for each weekday.
(v)
Timer operations which can be set in combination
Item
Item
Timer
OFF timer
ON timer
Weekly timer
Note (1) �: Allowed �: Not
() Since the ON timer, sleep timer and OFF timer are set in parallel, when the times to turn ON and OFF the air-conditioner are duplicated, the set-
ting of the OFF timer has priority.
(4)

Remote control display during the operation stop

When the operation is stopped (the power source is turned ON), it displays preferentially the "Room temperature", "Center/
Remote", "Filter sign", "Inspection" and "Timer operation".
(5)

Hot start (Cold draft prevention at heating)

(a) Operating conditions
When either one of following conditions either of (i) to (iv), the hot start control is performed.
(i) From stop to heating operation
(ii) From cooling to heating operation
(iii) From heating thermostat OFF to ON
(iv) After completing the defrost control (only on units with thermostat ON)
(b)
Contents of operation
(i) Indoor fan motor control at hot start
)
Within  minutes after starting heating operation, the fan mode is determined depending on the condition of
thermostat (fan control with heating thermostat OFF).
a)
Thermostat OFF
i) Operates according to the fan control setting at heating thermostat OFF.
ii) Even if it changes from thermostat OFF to ON, the fan continues to operate with the fan control at thermostat
OFF till the heat exchanger thermistor (ThI-R or R, whichever higher) detects °C or higher.
iii) When the heat exchanger thermistor (ThI-R or R, whichever higher) detects °C or higher, the fan
operates with the set airflow volume.
Sleep time
Set OFF timer by hour
Timer
OFF timer
Set ON timer by hour Set OFF timer by clock Set ON timer by clock
ON timer
Weekly timer
0
'14 • KX-SM-221
Weekly timer