8) Shutdown–Ice fills ice storage bin and presses BC actuator to open BC. Comp, FM,
GM, and X12 relay continue. X10 relay and X11 relay de-energize. 90 sec. low-water
safety timer starts. When 90 sec. low-water safety timer terminates, Comp and FM
de-energize. GM and X12 relay continue. 60 sec. GM delay timer starts. Once 60
sec. GM delay timer terminates, GM, X12 relay, and EH on -C model de-energize.
DV energizes. Reservoir and evaporator drain. DV remains energized until BC closes
again.
Diagnosis: Check that BC actuator paddle is activated and not sticking. Confirm BC
is open and X10 relay de-energizes. If not, see "II.D. Bin Control Check." Next, confirm
X11 relay de-energizes. If not, check for 24VAC at X10 relay #3 (R) to neutral (LBU).
If 24VAC is present, replace X10 relay. If X11 relay is de-energized, after 90 sec. confirm
Comp and FM de-energize. If not, check for 35VDC at CB #3 (BR) to CB #4 (DBU).
If 0VDC is present, replace X11 relay. If 35VDC is present and Comp and FM remain
energized, replace CB. 60 sec. after Comp and FM de-energize, confirm that GM and
X12 relay de-energize. If not, replace CB. Next, confirm DV energizes. If not, check for
24VAC at X12 relay #5 (W/R) to neutral (LBU) and X12 relay #1 (V) to neutral (LBU).
If 24VAC is present at X12 relay #5 (W/R) and not at #1 (V), replace X12 relay. If 24VAC
is present at X12 relay #1 (V) and DV is not energized, check for 24VAC at X10 relay
#6 (W/BK) to neutral (LBU) and X10 relay #2 (V) to neutral (LBU). If 24VAC is present
at X10 relay #2 (V) and not at #6 (W/BK), replace X10 relay. If 24VAC is present, check
DV coil continuity and replace as necessary. If DV coil is good, check for crimped drain
hose or clogged drain line.
Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer;
DV–drain valve; FM–fan motor; GM–gear motor; HPS–high-pressure switch;
LFS–lower float switch; UFS–upper float switch; WV–inlet water valve;
X10–control relay; X11–water control relay; X12–compressor delay relay