York YKFE12BXEXBH-RX Installation And Owner's Manual page 18

Table of Contents

Advertisement

Piping Procedure
3. Connection of piping
1)
Move the indoor tubing and drain hose to the hole.
□ Remove tubing holder and pull the tubing out of the chassis.
2)
Replace the tubing holder into original position.
Route the tubing and the drain hose straight backwards.
3)
4)
Insert the xonnecting cable into the indoor unit through the hole.
□ Do not connecting the cable to the indoor unit.
□ Make a small loop with the cable for easy connection later.
Tape the tubing and the connecting cable.
5)
6)
Indoor unit installation.
7)
Connecting the pipings to the indoor unit.
□ Align the center of the pipings and sufficiently tighten the flare nut
with fingers.
Finally, tighten the flare nut with torque wrench until the wrench
clicks.
□ When tightening the flare nut with torque wrench, ensure the
direction for tightening follows the arrow on the wrench.
Pipe
Tighten torque
size
1420~1720N.cm
ø6.35
(144~176kgf.cm)
3270~3990N.cm
ø9.52
(333~407kgf.cm)
4950~6030N.cm
ø12.7
(490~500kgf.cm)
6180~7540N.cm
ø15.88
(630~770kgf.cm)
9720~11860N.cm
ø19.05
(990~1210kgf.cm)
4. Precautions in bending
If it is necessary (locally purchased) to bend or stretch the
1)
tubing, use the spring which is attached to the tubing instead of
pipe bender.
□ Please make a careful notice to make a smooth line.
□ Hold the tubing with your two hands closely and then bend or
stretch it slowly not to make any crack.
□ Remember that the radius (R) should exceed 70mm. (Refer to
Fig.16)
Do not repeat the bending process to prevent the tubing from
2)
cracking or crushing.
Keep in mind that the bending part should not be cracked and
3)
make the radius (R) as long as possible. (Refer to Fig.17)
A (mm)
Flare shape
8.3~8.7
R0.4~0.8
12.0~12.4
12.4~16.6
18.6~19.0
22.9~23.3
Indoor unit tubing
Spanner
Fig. 15
Spanner
Flare nut
Pipings
Torque wrench
R70mm
Fig. 16
Fig. 17
15