Connecting the power supply

The 24 V DC load power supply required for the supply must be wired to the screw-type terminal
block (connector X124).
Note
The interface X124 is provided exclusively to connect the external power supply.
Properties of the load power supply
Danger to life from hazardous voltage when connecting an unsuitable power supply
The 24 V DC voltage must be generated as functional extra-low voltage with safe electrical
isolation (according to IEC 204-1, Chapter 6.4, PELV) and grounded by the user (establish
a connection between PELV signal M and central grounding point of the system).
Table 6-6
Parameter
Voltage range - mean value
Ripple
Non-periodic overvoltage
Rated current consumption
Starting current
Power consumption
Wiring the screw-type terminal block
Danger to life from energized parts
Death or serious injury will result if energized parts are touched.
Ensure that the system is de-energized when you wire the modules!
Use flexible cables with a cross-section of at least 1 mm² when you wire the power supply.
Wire-end sleeves are required if you wire several cables per connection.
1. Strip the cable ends.
2. Put on the wire-end sleeve if applicable.
3. Plug the cable end (with wire-end sleeve) into the screw-type terminal connection.
SIMOTION D410
Manual, 04/2014
WARNING
Electrical parameters of the required load power supply
DANGER
Values
Conditions
20.4...28.8 V DC
max. 5 %
at 24 V DC
max. 35 V DC
max. 500 ms, 50 s recovery time, max.
10 results/h.
0.8 A
Without DRIVE-CLiQ and digital outputs
3 A
Without Power Module, DRIVE-CLiQ and
digital outputs
20 W
Connecting
6.6 Connecting the power supply
75