2.2 Wiring LOGO!

Use a screwdriver with a head 3 mm wide to wire LOGO!.
You do not need wire end ferrules for the connectors. You can use wires up
to the following sizes:
S
2
1 x 2.5 mm
S
2
2 x 1.5 mm

2.2.1 Connecting the power supply

LOGO! 230R and LOGO! 230RC are suitable for line voltages with a rat-
ing of 115 V and 230 V and for mains frequencies of 50 Hz or 60 Hz. The
line voltage can be between 85 V and 264 V. At 230 V, LOGO! 230R/RC
consumes 26 mA of current.
LOGO! 24 and LOGO! 24R are suitable for supply voltage of 24 V DC.
The supply voltage can be between 20.4 V and 28.8 V. At 24 V,
LOGO! 24R consumes 62 mA of current, whereas LOGO! 24 consumes
30 mA plus current for the outputs of up to 4 x 0.3 ampere (1.2). (In the
case of LOGO! 24, the outputs are supplied by the 24 V supply voltage.)
Connecting
You connect LOGO! to the mains as follows:
L+
M
LOGO! 24
LOGO! 24R
Note
LOGO! has protective insulation. A ground terminal is not necessary.
LOGO! manual
EWA 4NEB 712 6006-02
Installing and wiring LOGO!
L1
N
LOGO! 230R
LOGO! 230RC
5