NOTICE
Device fault with missing equipotential bonding
An equipotential bonding conductor with a cross-section of at least 25 mm
between components in a system that are located at a distance from each other. If an
equipotential bonding conductor is not used, leakage currents that could destroy the Control
Unit or other PROFIBUS nodes can be conducted via the PROFIBUS cable.
PROFIBUS connector
The terminating resistors must be switched on at the first and last terminal in a line to ensure
uninterrupted communication.
The bus terminating resistors are activated in the connector.
The cable shield must be applied over a large area and on both sides.
Connectable devices
The following devices can be connected to the PROFIBUS DP interface:
● PG/OP programming devices
● SIMATIC HMI devices
● SIMATIC S7 controllers with PROFIBUS DP interface
● Distributed I/O
● Teleservice adapter
● Drive units with PROFIBUS DP interface (standard slaves)
4.5

PROFINET interface (SIMOTION D410 PN only)

PROFINET is an open component-based industrial communication system using Ethernet for
distributed automation systems.
SIMOTION D410 PN includes a PROFINET interface with 2 ports (X200 and X201).
The PROFINET interface supports operation of a SIMOTION D410 PN as an IO controller and/
or as an I device.
SIMOTION D410
Manual, 04/2014
Note
An overview of the components used with SIMOTION D410 is available in the
Catalog .
Take note of the documentation on the individual modules or devices!
4.5 PROFINET interface (SIMOTION D410 PN only)